Checking Automatic Operation - Champion Global Power Equipment 100199 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

8.
Verify that the gas pressure remains within the acceptable
parameters as listed in the manual, provided that you
placed a Manometer in line prior to starting this test.
9.
Let the HSB run under load for at least 30 minutes. With
the unit running listen for unusual noises, inspect for
vibrations or other unusual items that might reflect a
problem.
10. When the test process is completed, switch the ATS
Control Module to the ATS position. The ATS will transfer
back to UTILITY SUPPLY, this will power all circuits of the
home.
11. The HSB will run through a cool down cycle, shut down
and return to standby mode.
The test is now complete and the system is in standby mode.
CHECKING AUTOMATIC
OPERATION
To check the HSB system for proper automatic operation,
proceed as follows:
1.
Ensure the HSB is set in the OFF positions on both the
Engine Control Module and the ATS Module.
2.
Install front cover of the ATS.
3.
Return the Engine Control Module and the ATS Module
to their ATS positions. The HSB system is now ready for
automatic operation.
4.
Turn OFF the Utility Main Circuit Breaker.
5.
The engine should crank and start when the utility power
source is turned OFF.
6.
After starting, the ATS should connect load circuits to the
GENERATOR SUPPLY. Let the HSB system operate through
its entire automatic sequence of operation.
7.
Once the HSB system has run through its automatic
sequence of operation. Turn on the Utility Main Circuit
Breaker. The ATS should automatically transfer from
GENERATOR SUPPLY to UTILITY SUPPLY.
8.
The HSB will run through a cool down cycle, shut off and
be in standby ready mode.
9.
This check is now complete.
© 2015 Champion Power Equipment
INSTALLATION
CUSTOMER FAMILIARIZATION-
SUMMARY
It's important to educate the home owner on proper
maintenance, operation and service call procedures. A properly
educated home owner can reduce unnecessary service trips and
phone calls.
Ensure that the installation of the HSB and ATS has been
correctly performed as outlined by the manufacturer and that it
meets all applicable codes.
Test and confirm proper operation of the HSB and ATS system as
outlined in the appropriate installation and owner's manuals.
Educate the home owner on the location and operation of;
1.
Full flow shutoff valve
2.
Automatic operation of the HSB system
3.
Engine Control Module and LED indicators
4.
ATS Module and LED indicators
5.
Battery Charger and LED indicators
6.
Exterior fault code indicator LED on the backside of the
HSB
7.
ATS operation
8.
Exercise scheduled time of operation
9.
Scheduled Maintenance
10. Fill out and provide the customer a copy of the HSB,
ATS model & serial number reference. This information
is extremely important for part purchases and service
information, these numbers are specific to each HSB and
ATS.
11. Fill out and provide the customer a copy of the ATS back-
up circuits.
12. Fill out the Circuit Label inside the ATS.
It's always a good business practice to place business cards in
the Owner's and Installation manuals and place dealer stickers
on the HSB and ATS for the customer's reference.
Model 100199
Part No. 101049 Rev. B
43