Hsb Test; Voltage Checks- No Load - Champion Global Power Equipment 100199 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

1.
Wire land #1
Ground
2.
Wire land #2
L1
3.
Wire land #3
N
4.
Wire land #4
NOT CONNECTED EMPTY
5.
Wire land #5
B-
6.
Wire land #6
B+

HSB TEST

VOLTAGE CHECKS – NO LOAD
DANGER
!
Proceed with caution. Once the
Utility Power is turned ON, the ATS is
now electrically hot. The feeder lines
and terminals are now live. Contact
with these connections will result in
extremely hazardous and possibly
fatal electrical shock. Use the correct
procedures as described in national
electrical codes.
WARNING
!
The manufacturer recommends
!
that a licensed electrician or an
individual with complete knowledge
of electricity perform these
procedures.
© 2015 Champion Power Equipment
G (GREEN)
P (PINK)
W (WHITE)
B (BLACK)
R (RED)
INSTALLATION
1.
With the Engine Control Module and ATS Module both in
the OFF position.
2.
Turn ON the utility power supply to the ATS.
3.
With an AC voltmeter, check for the correct voltage.
Single-phase utility power supply. Measure across the
UTILITY SUPPLY ATS terminal lugs L1 and L2. Also check
L1 to NEUTRAL and L2 to NEUTRAL.
4.
The utility supply voltage should be correct and compatible
with the ATS ratings.
5.
Turn OFF the utility power supply to the ATS.
6.
The Control Panel MAIN CIRCUIT BREAKER must be in the
OFF position.
7.
Set the ATS module in the test mode.
8.
Set the Engine Control Module in the MANUAL mode. The
HSB will crank and start. Let the HSB warm up at no load
for 5 minutes to stabilize performance.
9.
Set the Control Panel MAIN CIRCUIT BREAKER in the ON
position.
DANGER
!
Proceed with caution. HSB generator
output voltage is now being delivered
to the ATS and is electrically hot. The
feeder lines and terminals are now
live. Contact with these connections
will result in extremely hazardous
and possibly fatal electrical shock
10. With an AC voltmeter, check the correct voltage. Single-
phase generator supply.
11. Measure across GENERATOR SUPPLY ATS lugs L1 and L2.
Also check L1 to NEUTRAL and L2 to NEUTRAL. These are
factory pre-set limits.
Model 100199
Part No. 101049 Rev. B
41