the battery voltage rises above 21.1 volts, the LED will turn off.
Battery voltage is NOT monitored when the engine is cranking,
just when the engine is running. If the YELLOW LED comes on
it will not shut the HSB off, it will remain lit until the battery
condition meets the required output.
When the LED remains lit, the battery charging should be
checked and the condition of the batteries. Follow reset
procedures contained in the manuals specific to your model to
clear or correct.
HIGH ENGINE TEMP. LED
The RED LED will be lit if the engine operating temperature
exceeds the factory preset limits. If excessive operating
temperature is detected, the HSB will shut down and re-start
will be disabled. The RED LEDs on the module and enclosure
exterior are lit.
This failure could be the result of an excessive load or high
ambient temperatures. Should this fault occur do the following;
1.
Open the enclosure doors to increase air flow throughout
the unit.
2.
Check oil level, add oil if required.
3.
Inspect the interior and exterior of the enclosure for debris,
leaves, ect., and remove them to increase air flow around
and inside the unit.
4.
Once the engine temperature falls into the normal
operating range, generally 30 minutes, follow the reset
procedures in the manuals specific to your model to clear
and correct fault.
5.
Close the enclosure doors and the unit is ready to run.
HZ OVER/UNDER SPEED LED
The RED LED will be lit if the engine was operating above or
below its preset speed limits. These limits are factory set to
protect the HSB and the circuits connected to the generator
output circuits. When this fault occurs, the HSB will shut down,
light the RED LED, shut down and re-start will be disabled. The
exterior fault code LED on the back of the HSB enclosure will be
activated and lit.
Appliances connected to the generator circuit could be damaged
from high generator output if the engine is allowed to operate
above the factory preset limits. If this failure occurs contact
Champion or your Authorized Champion Dealer. The RED LED will
remain lit until the failure has been corrected, the HSB will not
attempt to transfer or run.
© 2015 Champion Power Equipment
INSTALLATION
LOW OIL LED
The RED LED will be lit when the engine oil level drops below
the safe operating level. When this fault is detected, the HSB
will shut down and re-start will be disabled. RED LEDs on the
module and enclosure exterior are lit.
Check the oil level. The oil level should be at the FULL mark, if
necessary, add oil. DO NOT overfill. Inspect the unit for a possible
oil leak, if a leak is discovered, contact Champion or your nearest
Authorized Champion Dealer. Follow the reset procedures
contained in the manuals specific to your model to clear and
correct.
OVER CRANK LED
The RED LED will be lit if the engine failed to start after 5
attempts. This prevents the HSB from damaging itself or other
related components. When the fault is detected, the HSB will shut
down and re-start will be disabled. RED LEDs on the module and
exterior are lit.
This failure could be the result of insufficient fuel supply. Check
the in-line fuel shut off valves and make sure they are in the ON/
OPEN position. Position them in the correct position, follow the
reset procedures contained in the manuals specific to your model
to clear and correct. If they are in the correct position and the
HSB shows a fault light again, it's recommended to perform a
Monometer pressure check by an Authorized Champion Dealer or
installer. This will make sure the correct amount of fuel is being
delivered to the HSB when it starts.
Insufficient battery output could result in poor cranking cycles,
not permitting the engine starter to reach optimum starting RPM
to start the engine. This can be verified by checking the Battery
Charger LED, NO CHARGE. If this occurs, the individual battery
voltages must be checked to determine if the battery is properly
charged or if it has failed. It is extremely important to follow all
cautions and warning per the battery manufacturer concerning
installation, service, maintenance and replacement procedures.
RUN LED
The GREEN LED will be lit if the engine is running and is only lit
when the engine is running.
POWER LED
The GREEN LED will be lit, indicating the HSB is working correctly
and loads can be connected or transferred to it. It is only lit when
the HSB is running.
Model 100199
Part No. 101049 Rev. B
37