P0155 – Puissance de la Résistance de Freinage Dynamique
Plage
0,02 à 650,00 kW
Réglable :
Propriétés :
Accès aux groupes
01 GROUPES DE PARAMÈTRES
par l'IHM :
Description:
This parameter adjusts the trip level of the braking resistor overload protection.
It must be set according to the used braking resistor rated power (in kW).
Operation: if the average power dissipated on the braking resistor exceeds the value adjusted in P0155 for 2
minutes, the inverter will be disabled with F077 – DB Resistor Overload.
In order to get more details on the selection of the braking resistor, refer to the item 3.2.3.2 - Dynamic Braking, of
the user's manual.
28 Freinage Dynamique
Freinage Dynamique
Réglage
2,60 kW
d'Usine :