Freinage Dynamique
Le tableau suivant présente le niveau de déclenchement de surtension.
Steps to enable the dynamic braking:
Connect the braking resistor (Refer to the item 3.2.3.2 - Dynamic Braking, of the user's manual).
Set P0154 and P0155 according to the used braking resistor.
Set P0151 or P0185 at the maximum value: 400 V (P0296 = 0), 800 V (P0296 = 1, 2, 3 or 4), 1000
V (P0296 = 5, 6 or 7) or 1200 V (P0296 = 8), according to the case, in order to prevent the activation
of the DC voltage regulation before the dynamic braking.
P0154 – Dynamic Braking Resistor
Plage
Réglable :
Propriétés :
Accès aux groupes
par l'IHM :
Description:
Adjust this parameter with the ohmic value of the used braking resistor.
14
If P0154 = 0, the braking resistor overload protection is disabled. It must be programmed in zero if no braking
resistor is used.
14-2
Tableau 14.1 - Niveaux de déclenchement de surtension (F022)
V
Onduleur
nom
220/230 V
380 V
400/415 V
440/460 V
480 V
500/525 V
550/575 V
600 V
660/690 V
Tension de Liaison CC (U
P0153
U
nom
d
U
d
Tension Résist.
Freinage (DB)
Figure 14.1 - Courbe d'actionnement de freinage dynamique
0,0 à 500,0 ohm
01 GROUPES DE PARAMÈTRES
28 Freinage Dynamique
P0296
F022
0
> 400 V
1
2
> 800 V
3
4
5
6
> 1000 V
7
8
> 1200 V
) (P0004)
d
F022 - Surtension
Actionnement du freinage dynamique
Temps
U
d
Temps
Réglage
0,0 ohm
d'Usine :