Skip Frequencies
Setup::Application::Skip Frequencies
Function availability depends on macro selected.
This function is used to prevent the Drive operating at frequencies that cause mechanical resonance in the load.
PNO
Parameter Descriptions
1908
Skip Freq Band 1
The width of skip band 1 in Hz.
1909
Skip Frequency 1
The centre frequency of skip band 1 in Hz.
1910
Skip Freq Band 2
The width of skip band 2 in Hz.
1911
Skip Frequency 2
The centre frequency of skip band 2 in Hz.
1912
Skip Freq Band 3
The width of skip band 3 in Hz.
1913
Skip Frequency 3
The centre frequency of skip band 3 in Hz.
1914
Skip Freq Band 4
The width of skip band 4 in Hz.
1915
Skip Frequency 4
The centre frequency of skip band 4 in Hz.
Functional Description
Four programmable skip frequencies are available to avoid resonances within the mechanical system. Enter the value of frequency that causes
the resonance using a Frequency parameter and then program the width of the skip band using its Band parameter. The Drive will then avoid
sustained operation within the forbidden band as shown in the diagram. The skip frequencies are symmetrical and thus work in forward and
reverse.