Parameter Reference
Sequencing
Parameters::Motor Control::Sequencing
These parameters allow the user of the AC30V to monitor the status and affect the behaviour of the DS402 drive state machine as described in
detail in Appendix B "Sequencing Logic".
PNO
Parameter Descriptions
0591
Local
Local (GKP) of Control and Reference.
1565
Local Power Up Mode
The initial value of
0: AS WHEN POWERED DOWN
1: LOCAL
2: REMOTE
0592
Local Reference
Local Reference from GKP.
0610
App Control Word
Control Word from Application (Terminals).
0627
Comms Control Word
Control Word from Fieldbus.
0644
Control Word
Monitor (read-only) Control Word updated from the active source.
0661
Status Word
This is the DS402 Status Word
0678
Sequencing State
Drive DS402 Sequencing State.
0679
Switch On Timeout
Time allowed for line contactor to close when entering the Switched On state from Switched Off state. If this time is non-zero, a Line
Contactor trip will occur if the DC Link Voltage remains low until the timeout expires. If the timeout is set to zero, an Under Voltage
trip will occur immediately.
0680
App Reference
Reference from terminals (via. the application)
Local can be selected by the User using this enumerated parameter.
0591
the state when the Drive was powered down (default)
always powers up with
always powers up with
Local set to TRUE
0591
Local set to FALSE
0591