Parker AC30V Série Manuel Technique page 271

Masquer les pouces Voir aussi pour AC30V Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Graphical Keypad
Setup::Environment
Parameters::Keypad::Graphical Keypad
PNO
Parameter Descriptions
1141
View Level
The view level may be used as a convenient method to hide menus and parameters not currently required. The view levels are:
0
Operator – only the "Control Screen", "Favourites", "Setup" and "Monitor" menus are visible.
1
Technician – additional menus are visible in the "Setup" and "Monitor" menus
2
Engineer – the "Parameters" menu is visible in addition to the above.
0982
Startup Page
On power-up the GKP briefly displays the drive name, rating and software version. After a short timeout the display automatically
changes to the menu defined here
0
Default
1
Control Screen
2
Favourites
3
Monitor
When Startup Page is set to "Default" the first menu will be:
*
*
*
0983
Display Timeout
When the GKP is idle, (no keys pressed), for a period longer than the Display Timeout, the display will automatically revert to the
menu defined in the Startup Page parameter.
Setting the Display Timeout to zero defeats this feature.
1142
GKP Password
Defines the password to be entered to allow modification to parameters using the GKP. This password does not affect access via the
web page. A value of 0000, (the default value), inhibits the password feature. Entering a value other than 0000 causes the GKP to
prompt for the password before proceeding to the parameter edit mode.
Once a password has been entered the GKP remains unlocked. To re-lock the password return to the top of the menu tree then
press Soft Key 1.
1097
Password in Favourite
When the GKP Password is active this parameter may be used to selectively defeat the password feature in the Favourites menu. By
default this parameter is FALSE, meaning that the password is ignored when modifying Favourites parameters.
AC30V series Variable Speed Drive
The "Control Screen" menu if the drive is in local sequencing mode, otherwise
The "Favourites" menu if the Favourites menu is not empty, otherwise
The "Monitor" menu.
D-45
Parameter Reference

Publicité

Table des Matières
loading

Table des Matières