D-84
Parameter Reference
Ramp
Parameters::Motor Control::Ramp
This function forms part of the reference generation. It provides the facility to control the rate at which the Drive will respond to a changing
setpoint demand.
PNO
Parameter Descriptions
0484
Seq Stop Method VHz
Volts/Hz control mode only
Selects stopping mode that the controller will use once the run command has been removed. The choices are:
Enumerated Value : Stopping Mode
0 : DISABLED VOLTAGE, (COAST)
1 : RAMP
2 : STOP RAMP
3 : DC INJECTION
When DISABLED VOLTAGE ( COAST ) is selected the motor will free-wheel. When RAMP is selected the Drive will decelerate using
the reference ramp deceleration time, provided it is non-zero. When STOP RAMP is selected the motor will decelerate in Stop Ramp
Time. When DC INJECTION is selected the motor is stopped by applying dc current.
1257
Seq Stop Method SVC
All Control modes except Volts/Hz
Selects stopping mode that the controller will use once the run command has been removed. The choices are:
Enumerated Value : Stopping Mode
0 : DISABLED VOLTAGE, (COAST)
1 : RAMP
2 : STOP RAMP
When DISABLED VOLTAGE ( COAST ) is selected the motor will free-wheel. When RAMP is selected the Drive will decelerate using
the reference ramp deceleration time, provided it is non-zero. When STOP RAMP is selected the motor will decelerate in Stop Ramp
Time.
0485
Ramp Type
Select the ramp type:
Enumerated Value : Ramp Type
0 : LINEAR
1 : S Ramp