Parameter Reference
PNO
Parameter Descriptions
1541
Power Parameters
If the parameter 1538 Full Restore is set to PARTIAL, then the parameter Power Parameters allows the user to load the 'power'
parameters from the file, leave the current values or set the values to the defaults.
Notes:
-
If the power stack of the drive is different to the power stack from which the clone file was saved and the user chooses LOAD
FROM FILE then the clone load will not be permitted. However the clone load will be permitted if the control module on which
the user is restoring is not attached to a power stack, or if LEAVE CURRENT VALUES or SET TO DEFAULT VALUES is chosen
instead.
-
The power parameters cannot be restored from a clone file that was saved on a control module with the parameter 0989 Power
Stack Required set to NONE.
Enumerated Value : Power Parameters
1540
Other Parameters
If the parameter 1538 Full Restore is set to PARTIAL, then the parameter Other Parameters allows the user to load the 'other'
parameters from the file, leave the current values or set the values to the defaults.
Enumerated Value : Power Parameters
1542
Clone Start
When TRUE this parameter starts the cloning process, either saving or loading depending on the parameter 1537 Clone Direction.
The cloning process will only start if the parameter 1543 Clone Status is IDLE.
Once the cloning has completed the parameter 1543 Clone Status will be DONE. Set the Clone Start parameter back to FALSE to
return to the IDLE state.
0 : LOAD FROM FILE
1: LEAVE CURRENT VALUES
2 : SET TO DEFAULT VALUES
0 : LOAD FROM FILE
1: LEAVE CURRENT VALUES
2 : SET TO DEFAULT VALUES
AC30V series Variable Speed Drive