Functional Description
The table below describes how Output is controlled by Raise Input, Lower Input and Reset Input.
Reset
TRUE
FALSE
FALSE
FALSE
FALSE
* If Output is greater than Maximum Value the Output will ramp down to Maximum Value at Ramp Time. If Output is less than
Minimum Value the Output will ramp up to Minimum Value at Ramp Time.
IMPORTANT:
If Maximum Value is less than or equal to Minimum Value, then Output is set to Maximum Value.
AC30V series Variable Speed Drive
Raise Input
Raise Output
Any
Any
TRUE
FALSE
FALSE
TRUE
FALSE
FALSE
TRUE
TRUE
Output tracks Reset Value
Output ramps up to Maximum Value at Ramp Time
Output ramps down to Minimum Value at Ramp Time
Output not changed. *
Output not changed. *