Parker AC30V Série Manuel Technique page 294

Masquer les pouces Voir aussi pour AC30V Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

D-68
Parameter Reference
PMAC Flycatching
Parameters::Motor Control::PMAC Flycatching
This block performs a directional speed search. It allows the Drive to seamlessly catch a spinning motor before controlling the motor to the
desired setpoint. This is especially useful for large inertia fan loads, where drafts in building air ducts can cause a fan to `windmill'.
PNO
Parameter Descriptions
0689
PMAC Flycatching Enable
Enable the flycatching for PMAC motor
0690
PMAC Fly Search Mode
The PMAC Flycatching sequence can be triggered by different starting conditions:
ALWAYS:
TRIP or POWER-UP: After uncontrolled stop, i.e. trip or coast, or after a power-up
TRIP:
0691
PMAC Fly Search Time
PMAC Fly Search Time to catch the right speed
0692
PMAC Fly Load Level
PMAC Fly Load Level during fly catching
0693
PMAC Fly Active
Diagnostic to show if the PMAC fly catching is active or inactive
0694
PMAC Fly Setpoint
PMAC Fly Setpoint
Functional Description
The flycatching function enables the drive to be restarted smoothly into a spinning motor.
All starts (after controlled or uncontrolled stop, or after a power-up)
After uncontrolled stop, i.e. trip or coast
AC30V series Variable Speed Drive

Publicité

Table des Matières
loading

Table des Matières