D-82
Parameter Reference
Raise Lower
Setup::Application::Raise Lower
Monitor::Application::Raise Lower*
Appears when the Raise/Lower macro is selected.
The Raise/Lower function acts as an internal motorised potentiometer (MOP) used as a reference source.
PNO
Parameter Descriptions
1901
RL Ramp Time
Rate of change of the Output. Defined as the time to change from 0.00% to 100.00% . Note that the raise and lower rates are
always the same.
1902
RL Reset Value
The value Output is set to when the Reset Input is TRUE.
1903
RL Maximum Value
The maximum value to which Output will ramp up to.
1904
RL Minimum value
The minimum value to which Output will ramp down to.
Reset Input
This is connected to a Digital Input as part of the selected Macro. When TRUE forces Output to track Reset Value.
Raise Input
This is connected to a Digital Input as part of the selected Macro. When TRUE causes Output to ramp up.
Lower Input
This is connected to a Digital Input as part of the selected Macro. When TRUE causes Output to ramp down.
1905
Raise Lower Output*
The ramp output monitor. Output is preserved during the power-down of the Drive.
AC30V series Variable Speed Drive