D-54
Parameter Reference
PNO
Parameter Descriptions
0039
Anin 01 Value
Terminal X11.1
The value returned by the signal processing electronics. For unipolar ranges, (all except -10..10V), the value is expressed as a
percentage of the hardware range. For the -10..10V range the full range signal is expressed as -100% to +100%.
0040
Anin 01 Break
When the input range is set to 4..20mA a break is defined as an input signal less than 3mA. Otherwise this parameter is set to
FALSE.
0041
Anin 02 Value
Terminal X11.2
The value returned by the signal processing electronics. For the 0..10V range the value is expressed as a percentage of the
hardware range, (0 to 100%). For the -10..10V range the full range signal is expressed as -100% to +100%.
0042
Anout 01 Value
Terminal X11.3
The desired output value expressed as a percentage of the output range.
0043
Anout 02 Value
Terminal X11.4
The desired output value expressed as a percentage of the output range.
Range
Mapping
0..10V
0% gives 0V, 100% gives 10V
0..20MA
0% gives 0mA, 100% gives 20mA
4..20MA
0% gives 4mA, 100% gives 20mA
Range
Mapping
-10..10V
-100% gives -10V, 100% gives 10V
0..10V
0% gives 0V, 100% gives 10V
AC30V series Variable Speed Drive