Technical data
Menu
Default setting
Fault relay
dynamic
dynamic or static
(FAIL - FREQ)
15.6.4 Sensor-specific values
Further specifications are provided in the instructions for use
for the relevant sensor.
15.6.4.1 Polytron 5100 EC
Menu
Default setting
A1 alarm
sensor-dependent
A2 alarm
sensor-dependent
2-wire / 3-wire (Set
3-wire
2-3)
15.6.4.2 Polytron 5200 CAT
DrägerSensor DQ
Menu
Default setting
A1 alarm
20 %LEL
A2 alarm
40 %LEL
DrägerSensor LC
Menu
Default setting
A1 alarm
2.0 %LEL
A2 alarm
4.0 %LEL
15.6.4.3 Polytron 5310 IR
Menu
Default setting
A1 alarm
20 %LEL
A2 alarm
40 %LEL
15.6.4.4 Polytron 5700 IR
Type 334
Menu
Default setting
Test gas
Methane
Test gas units
%LEL
Test gas concen-
50 %LEL
trations
30
Range
Menu
dynamic / static
A1 alarm
A2 alarm
LEL type
Measured gas
Units of measured
gas
Full scale setting
Range
PIR LOCK
Range
PIR password
1 to 100
Type 330
Menu
Range
Test gas
0.1 to 10
Test gas units
Test gas concen-
trations
Range
1 to 100
Range
A1 alarm
A2 alarm
LEL type
If the unit is Vol%
and FSD < 10,
Measured gas
range: {0.01 to
FSD}
Units of measured
If the unit is Vol%
gas
and
10 ≤ FSD < 100,
range: {0.1 to FSD}
If the unit is %LEL
or ppm and
FSD ≥ 100, range:
{1 to FSD}
Default setting
20 %LEL
40 %LEL
NIOSH
Methane
%LEL
100 %LEL
off
_ _ _2 (3x blank
spaces, then 2)
Default setting
Propane
%LEL
50 %LEL
20 %LEL
40 %LEL
NIOSH
Propane
%LEL
Instructions for use
|
Dräger Polytron 5000 Series
Range
0.01 to 100 Vol%
with %LEL = 0.3 to
100 %LEL
IEC / PTB / NIOSH
/ configurable
%LEL / Vol% / PPM
Unit is Vol%, FSD
options: {1, 2, 5, 10,
20, 30, 50,100}
Unit is %LEL. FSD
options: {20, 50,
100}
Unit is ppm, FSD
options: {500,
1000, 2000, 5000,
9999}
on/off
Range
If the unit is Vol%
and FSD < 10,
range: {0.01 to
FSD}
If the unit is Vol%
and
10 ≤ FSD < 100,
range: {0.1 to FSD}
If the unit is %LEL
or ppm and
FSD ≥ 100, range:
{1 to FSD}
0.01 to 100 Vol%
with %LEL = 0.3 to
100 %LEL
IEC / PTB / NIOSH
/ configurable
%LEL / Vol% / PPM