IMPORTANT: Once the association has been made between 2 or more devices, a pop-up appears on the display asking you to extend
the configuration. This happens in the case where the devices have different configuration parameters (e.g. setpoint SP, RP etc.).
Pressing + on a pump extends the configuration of that pump to the other associated pumps. When the + key is pressed pop-ups
appear with the message "Wait...", and when this message is finished the pumps will start to work regularly with the sensitive
parameters aligned; refer to paragraph 11.4.5 for further information.
Disassociation of devices:
To dissociate a device belonging to an existing group, go to page AS (installer menu) of the device itself and press the – key for at least 5 seconds.
After this operation all the icons related to the connected devices will be replaced the message "No Dev" is shown and the COMM led will remain off.
Replacing devices:
To replace a device in an existing group it is sufficient to dissociate the device to be replaced and to associate the new device as described in the
procedures above. If it is not possible to dissociate the element to be replaced (faulty or not available), you will have to carry out the disassociation
procedure for each device and create a new group.
PR: Remote pressure
sensor
9.6 TECHNICAL ASSISTANCE MENU
Advanced settings to be made only by skilled personnel or under the direct control of the service network.
From the main menu, hold down simultaneously the "MODE" and "SET" keys until "SP" appears on the display (or use the selection menu pressing + or -
). The menu allows you to view and modify various configuration parameters: the MODE key allows you to scroll through the menu pages, the + and –
keys allow you respectively to increase and decrease the value of the parameter concerned. Press SET to leave this menu and return to the main menu.
The PR parameter is used to select a remote pressure sensor.
The default setting is with no sensor present. In order to execute its intended functions, the remote sensor must
be connected to a control unit, which in turn must be associated to the e.sybox, see point 5.1 - Operation with
control unit As soon as a connection is established between the e.sybox and control unit and the remote pressure
sensor has been connected, the sensor starts operating. When the sensor is active, the display shows an icon of
a stylised sensor with a P inside it. The remote pressure sensor operates in synergy with the internal sensor so
that the pressure never falls below the setpoint pressure in either of the two points in the system (internal and
remote sensors). This allows compensation for any pressure drops.
NOTE: in order to maintain the setpoint pressure in the point with lower pressure, the pressure in the other point
may be higher than the setpoint pressure.
ENGLISH
57