Changing the fault response <1>
p2100
[0]
0. F_no F response
[1]
1. F_no F response
[19]
19. F_no F response
Changing the acknowledge mode <1>
p2126
[0]
0. Fault_no ackn_mode
[1]
1. Fault_no ackn_mode
[19]
19. Fault_no ackn_mode
<1> The fault response, acknowledge mode and message type for all faults and alarms are set to meaningful default values in the factory setting.
Changes that may be required are only possible in specific value ranges specified by SIEMENS.
When the message type is changed, the supplementary information is tranferred from fault value r0949 to alarm value r2124 and vice versa.
1
2
DO: All objects
Diagnostics - Faults/alarms configuration
p2101
[0]
Fault response
0 = NONE
[1]
Fault response
1 = OFF1
2 = OFF2
3 = OFF3
5 = STOP2
6 = IASC/DCBRK
7 = ENCODER (p0491)
[19]
Fault response
p2127
[0]
Acknowledge mode
1 = Acknowledgement is only possible using POWER ON
[1]
Acknowledge mode
2 = Acknowledgement IMMEDIATELY after the cause has been removed.
3 = Acknowledge only when the PULSES ARE INHIBITED.
[19]
Acknowledge mode
3
4
Changing the message type (fault <==> alarm) <1>
p2118
[0]
0. Fault/alarm code
[0]
[1]
1. Fault/alarm code
[1]
[19]
19. Fault/alarm code
[19]
5
6
Function diagram
fp_8075_51_eng.vsd
SINAMICS
22.01.14 V04.07.00
Background
p2119
Fault/alarm type
1 = Fault (F)
Fault/alarm type
2 = Alarm (A)
3 = No message(N)
Fault/alarm type
7
8
- 8075 -