Signal targets for E_STW1
Signal
Meaning
= ON (close pre-charging/line contactor, pulses can be enabled)
STW1.0
0 = OFF1 (reduce Vdc along a ramp, suppress pulse and open pre-charging/line contactor)
1 = No OFF2 (enable is possible)
STW1.1
0 = OFF2 (immediate pulse suppression and switching on inhibited)
STW1.2
Reserved
1 = Enable operation (pulses can be enabled)
STW1.3
0 = Inhibit operation (suppress pulses)
STW1.4
Reserved
STW1.5
1 = Infeed, inhibit motoring operation
STW1.6
1 = Infeed, inhibit regenerative operation
STW1.7
= Acknowledge faults
STW1.8
Reserved
STW1.9
Reserved
STW1.10
1 = Control via PLC
STW1.11
Reserved
STW1.12
Reserved
STW1.13
Reserved
STW1.14
Reserved
STW1.15
Reserved
<1> Used in telegram 370.
<2> STW1.10 must be set to ensure that the drive object accepts the process data (PZD).
<3> Only for A_INF, S_INF
<4> Only for A_INF
1
2
DO: A_INF, B_INF, S_INF
PROFIdrive - E_STW1 control word infeed interconnection
Interconnection
parameters
p0840[0] = r2090.0
p0844[0] = r2090.1
p0852[0] = r2090.3
<3>
<4>
p3532= r2090.5
p3533= r2090.6
<3>
p2103[0] = r2090.7
<2>
p0854[0] = r2090.10
<5> B_INF and S_INF only for S120.
<6> Only for S120 and G150
<7> Not for G130.
3
4
[Function diagram] internal control word
A_INF
B_INF <6>
S_INF <5>
[8920.3]
[8720.3]
[8820.3]
[8920.3]
[8720.3]
[8820.3]
-
-
-
[8920.3]
-
[8820.3]
-
-
-
-
[8920.3]
-
-
[8920.3]
-
[8820.3]
[2546.3]
-
-
-
-
-
-
-
-
[8920.3]
[8720.3]
[8820.3]
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
5
6
fp_2447_54_eng.vsd
27.06.13 V04.07.00
PROFIdrive sampling time
<1>
<7>
[Function diagram] signal target
Inverted
A_INF
B_INF <6>
S_INF <5>
[8932]
[8732]
[8832]
-
[8932]
[8732]
[8832]
-
-
-
-
-
[8932]
-
[8832]
-
-
-
-
-
[8920]
-
-
-
[8920]
-
[8820]
-
[8060]
-
-
-
-
-
-
-
-
-
[8920]
[8720]
[8820]
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7
8
Function diagram
- 2447 -