Siemens SINAMICS G130 Mode D'emploi page 1095

Masquer les pouces Voir aussi pour SINAMICS G130:
Table des Matières

Publicité

Signal targets for STW1_BM
Signal
Meaning
0 = OFF (OFF1)
STW1.0
= ON
0 = OFF2 (immediate pulse suppression and switch on inhibit)
STW1.1
1 = No OFF2 (enable is possible)
0 = OFF3 (braking along the OFF3 ramp (p1135), then pulse suppression and switch on inhibit)
STW1.2
1 = No OFF3 (enable is possible)
0 = Inhibit operation
STW1.3
1 = Enable operation
0 = Inhibit ramp-function generator
STW1.4
1 = Operating condition
0 = Stop the ramp-function generator
STW1.5
1 = Enable the ramp-function generator
0 = Inhibit setpoint = 0
STW1.6
1 = Enable setpoint
STW1.7
= Acknowledge faults
STW1.8
Reserved
STW1.9
Reserved
STW1.10
1 = Control via PLC
STW1.11
Reserved
STW1.12
Reserved
STW1.13
Reserved
STW1.14
Reserved
STW1.15
Reserved
<1> Used in telegram 220.
<2> STW1.10 must be set to ensure that the drive object accepts the process data (PZD).
<3> Interconnection is not disabled.
1
2
DO: SERVO, VECTOR
PROFIdrive - STW1_BM control word, metal industry interconnection
p0854[0] = r2090.10
<2>
<3>
<3>
<3>
<3>
3
4
Interconnection
[Function diagram]
[Function diagram]
parameters
internal control word
signal target
p0840[0] = r2090.0
[2501.3]
p0844[0] = r2090.1
[2501.3]
p0848[0] = r2090.2
[2501.3]
p2816[0] = r2090.3
[2501.3]
p1140[0] = r2090.4
[2501.3]
[3060] [3070] [3080]
p1141[0] = r2090.5
[2501.3]
p1142[0] = r2090.6
[2501.3]
[3060] [3070] [3080]
p2103[0] = r2090.7
[2546.1]
-
-
-
-
[2501.3]
-
-
<3>
-
<3>
-
-
<3>
-
<3>
5
6
fp_2425_54_eng.vsd
27.06.13 V04.07.00
<1>
PROFIdrive sampling time
Inverted
[2610]
-
[2610]
-
[2610]
-
[2634.3]
-
-
[3060] [3070]
-
-
[8060]
-
-
-
-
-
[2501]
-
-
-
-
-
-
-
-
-
-
-
7
8
Function diagram
- 2425 -
S120/S150/G130/G150

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Sinamics g150

Table des Matières