Télécharger Imprimer la page

Reflex Servimat M Mode D'emploi Original page 47

Masquer les pouces Voir aussi pour Servimat M:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 52
ER Code
Alarm
01
Minimum pressure
02
Insufficient water
03
High water
04.1
Pump
05
Pump run time
06
Make-up time
07
Make-up cycles
08
Pressure measurement
09
Level sensor
10
Maximum pressure
11
Make-up quantity
14
Discharge period
15
Make-up valve
16
Power failure
18
Parameter
19
Stop ˃ 4 hours
20
Max. Make-up volume
21
Maintenance recommended
Floating
Causes
contact
YES
Set value not reached.
Water loss in the system.
Pump fault.
Controller in Manual mode
-
Set value not reached.
Make-up disabled.
Air in the system.
Solenoid valve does not open.
YES
Set value exceeded.
Make-up disabled.
Manual over supply.
Water intake through a leak in a
thermal transfer medium of the
user.
"VG" primary tank too small.
YES
Pump disabled.
Pump jammed.
Pump motor defective.
Pump motor contactor tripped.
Fuse defective.
-
Set value exceeded.
Severe water loss in the system.
Cap valve at the intake side
closed.
Air in the pump.
Control ball valve RKH1 in the
pressure relief pipe does not
close.
-
Set value exceeded.
Water loss in the system.
Make-up line not connected.
Make-up rate insufficient.
Make-up hysteresis too low.
-
Set value exceeded.
YES
Controller receives incorrect
signal.
YES
Controller receives incorrect
signal.
-
Set value exceeded.
Pressure relief pipe not
functioning.
Dirt trap clogged.
-
"With water meter" must be activated in
the Customer menu.
Set value exceeded.
Severe water loss in the system.
-
Set value exceeded.
Degassing pipe closed.
Dirt trap clogged.
-
Contact water meter measures
without make-up requirement.
-
No power.
-
Parameter settings incorrect.
-
Device is in Stop mode for more
than 4 hours.
-
Set value exceeded.
-
Set value exceeded.
Servimat M/L — 25.07.2024
Remedy
Check set value in the Customer or Service
menu.
Check water level.
Check pump.
Set the controller to Automatic mode.
Check set value in the Customer or Service
menu.
Clean the dirt trap.
Check functioning of the "PV1" solenoid
valve.
If necessary, manually add water.
Check set value in the Customer or Service
menu.
Check functioning of the "WV" solenoid
valve.
Drain water from the "VG" tank.
Check site heat transfer medium for leaks.
Rotate the pump with screwdriver.
Replace the pump motor.
Electrically test the pump motor.
Replace the fuse.
Check set value in the Customer or Service
menu.
Check the water loss and correct, if
necessary.
Open the cap valve.
Vent the pump.
Check the control ball valve RKH1 for correct
function.
Check set value in the Customer or Service
menu.
Check water level.
Connect make-up pipe
Check set value in the Customer or Service
menu.
Seal any leak in the system.
Connect the plug.
Check functioning of the pressure sensor.
Check the cable for damage.
Check the pressure sensor.
Check functioning of the load cell.
Check the cable for damage.
Connect the plug.
Check set value in the Customer or Service
menu.
Check functioning of the pressure relief pipe.
Clean the dirt trap.
Check set value in the Customer or Service
menu.
Check water loss in the system and repair, if
necessary.
Check degassing line.
Check dirt trap.
Check the make-up valve for leaks.
Connect to power supply.
Check settings, if necessary make basic
settings in the service menu.
Set the controller to Automatic mode.
Reset the "Make-up quantity" meter in the
Customer menu.
Perform maintenance and reset the
maintenance counter upon completion.
Controller
Alarm
reset
"Quit"
-
-
"Quit"
-
"Quit"
"Quit"
"Quit"
"Quit"
"Quit"
"Quit"
"Quit"
-
-
"Quit"
"Quit"
English — 47

Publicité

loading

Ce manuel est également adapté pour:

Servimat l