Controller
9.3.5
Setting degassing programmes
1.
Press "Settings".
–
The controller switches to the setting area.
2.
Press "Customer >".
–
The controller opens the Customer menu.
3.
Press "Degassing >".
–
The controller switches to the selected area.
–
Use the scroll bar to navigate through the list.
4.
Press "(012) Degassing programme".
–
The controller opens the list of degassing programmes.
5.
Press the desired button.
–
"Continuous degassing" is selected in this example.
No degassing and interval degassing are deselected.
–
Confirm your selection with "OK".
–
Degassing is deactivated.
46 — English
6.
Press "(013) Time, continuous degassing".
7.
Set the time for continuous degassing.
–
Use the "Left" and "Right" buttons to select the display value.
–
Use the "Up" and "Down" buttons to change the display value.
–
Confirm your entries with "OK".
Press "i" to display a help text for the selected area.
Press "X" to cancel your input without saving the new settings. The controller
automatically opens again the list.
9.4
Messages
The messages are impermissible deviations from the normal state. They can be
output either via the RS-485 interface or via two floating message contacts.
The controller displays the messages with a help text.
Message causes can be eliminated by the operator or a specialist workshop. If this
is not possible, contact the Reflex Customer Service.
Note!
When the cause for the message is eliminated, you must acknowledge the
fault with "OK" at the controller's operator panel.
Note!
Floating contacts, setting in the Customer menu, 9.3.1 "Customer
menu", 44.
To reset a fault message, proceed as follows:
1.
Touch the display.
–
The current fault messages are displayed.
2.
Touch a fault message.
–
The system displays the possible causes of the fault.
3.
When the fault is eliminated, confirm the fault with "OK".
Servimat M/L — 25.07.2025