Use only the supplied connection sets, 6.3.4 "Tank installation",
35.
•
Perform a calibration of the filling level when the primary vessel is aligned
and fully emptied, 9.3.1 "Customer menu", 44.
Standard values for level measurements:
Primary vessel
Measuring range
200 l
0 – 4 bar
300 – 500 l
0 – 10 bar
600 – 1000 l
0 – 25 bar
1500 – 2000 l
0 – 60 bar
3000 – 5000 l
0 – 100 bar
6.4
Electrical connection
DANGER
Risk of serious injury or death due to electric shock.
If live parts are touched, there is risk of life-threatening injuries.
•
Ensure that the supply cable to the device is disconnected and secured
against being switched back on.
•
Ensure that the system is secured and cannot be reactivated by other
persons.
•
Ensure that installation work for the electric connection of the device is
carried out by an electrician, and in compliance with electrical locally
applicable electrical engineering regulations.
For the electrical connection, you must differentiate between a connection
component and an operating component.
6.4.1
Terminal plan, connection component
1
Connection unit
2
Covers of the operating unit (folding)
•
•
3
Operating unit (Control Touch controller)
4
Cable bushings
5
Covers of the connection unit (folding)
•
•
•
The following descriptions apply to standard systems and are limited to the
necessary user-provided connections.
1.
Shut down the system and secure it against unintentional reactivation.
2.
Remove the covers.
DANGER – electric shock! Risk of serious injury or death due to electric
shock. Some parts of the device's circuit board may still be live with 230 V
even after the device has been physically isolated from the power supply by
pulling out of the mains plug. Before you remove the covers, completely
isolate the device controller from the power supply. Verify that the main
circuit board is voltage-free.
3.
Insert a suitable screwed cable gland for the cable bushings at the rear of the
connection component. M16 or M20, for example.
4.
Thread all cables to be connected through the cable glands.
5.
Connect all cables as shown in the terminal diagrams.
–
Connection unit, 6.4.1 "Terminal plan, connection component",
37.
–
Operating unit, 6.4.2 "Terminal plan, operating unit", 38.
–
When providing fusing for the appliance, note its connected load, 5
"Technical data", 33.
6.
Install the cover.
7.
Connect the mains plug to the 230 V power supply.
8.
Activate the system.
The electrical connection is completed.
Servimat M/L — 25.07.2024
RS-485 interfaces
Pressure output
Supply and fusing
Floating contacts
Aggregate connection
Installation
English — 37