Adjustment and functions
5.3.4.
Current output
This function makes it possible to modify the default flow rate range associated to the
4-20 mA current range. Usually the minimum valu of the flow rate range is associated to the
4 mA current and the maximum value of the flow rate range to the 20 mA current, for ins-
tance the flow rate range 0 to 180 l/min corresponds to the 4-20 mA current range.
The current output can however be inverted by inverting the flow rate range. Associate the
maximum value of the flow rate range to the 4 mA current and the minimal value of the flow
rate range to the 20 mA current: The flow rate range 0-180 l/min, for instance, then corres-
ponds to the 20-4 mA current range.
The units and number of decimal digits are those set within the "UNIT" function.
CURRENT
PULSE
→
If you do not want to adjust another parameter, go to the "END" parameter of the Set-
tings mode and press the "ENTER" key to save the settings and go back to the Read
mode.
5.3.5.
Pulse output
This function makes it possible to input the volume of liquid corresponding to a pulse.
→
Choose the unit then input the volume.
Example: a pulse is emitted every 5 m
PULSE
RELAY
→
If the message "PU H LIM" or "PU L LIM" is displayed, see chap.
→
If you do not want to adjust another parameter, go to the "END" parameter of the Set-
tings mode and press the "ENTER" key to save the settings and go back to the Read
mode.
4= 0000
Input the flow rate corresponding to a 4 mA
current.
4= 0000
3
volume has passed through the device.
L
M3
USGAL
IMPGAL
E-43-
Flow transmitter 8025/8035
20= 0000
Input the flow rate corres-
ponding to a 20 mA current.
20= 0180
PU = 000.00
Input the volume corre-
sponding to 1 pulse
PU = 005.00
6.2 .