→
Retighten the 4 screws on the cover in an alternating pattern.
Fig. 15 : Position of the cover on the 8041 transmitter
8.3.1.
Wiring the 4-20 mA current output
danger
Risk of injury due to electrical voltage
•
Before starting work, make sure that you switch off the supply
voltage and secure it to prevent restarting.
The current output on the 8041 can be connected in source mode
or sink mode.
→
Position the switch on the electronic board to the source mode
or sink mode position (see Fig. 16 or Fig. 17 ).
→
Connect the 4-20 mA output in source mode (see
sink mode (see Fig. 17 ).
→
Earth the device (see
Fig. 16 or Fig. 17 ).
22
Fig. 16 ) or
English
Type 8041
Installationandwiring
4-20 mA input
+
-
Switch on
source mode
4...20
* If a direct earthing connection is not possible, fit a 100 nF/50V capacitor
between the negative terminal of the power supply and the earth.
Fig. 16 : Current output connection in source mode
4-20 mA input
+
-
Switch on sink
mode
4...20 V+ V- PE Pls+Pls-
* If a direct earthing connection is not possible, fit a 100 nF/50V capacitor
between the negative terminal of the power supply and the earth.
Fig. 17 : Current output connection in sink mode
300 mA
Power supply
+
-
18-36 VDC
*
I
1 2 3 4 5 6
V+ V- PE Pls+Pls-
300 mA
Power supply
+
-
18-36 VDC
*
I
1 2 3 4 5 6