Installation and electrical wiring
Connection of the pulse output in NPN mode
(*) If direct earthing is not possible, insert a 100 nF / 50 V condensator between the negative terminal of the
voltage supply and the earth.
Fig. 32 :
Connection of the pulse ouput in NPN or PNP mode, of a compact version,
115/230 VAC, with relays, with cable glands
4.2.9.
Connection of the flow sensor to a remote
transmitter 8025
Configure the FLOW SENSOR selector on the electronic board (see chap.
Connect the remote flow sensor to the FLOW SENSOR terminal block of the electronic
board by respecting the pin assignment depending on the output type of the remote
sensor, either sinus (COIL) or pulse output (NPN).
Sensor with a sinus output
PLC
Switch to select either
115 VAC or 230 VAC
115/230 VAC power
supply
Shielding of the sensor cable
NC = Not connected
E-32-
Flow transmitter 8025/8035
Connection of the pulse output in PNP mode
Pulse, NPN
V-
V+
Shielding of the sensor
cable
Sensor with a pulse output (NPN)
PLC
Switch to select either
115 VAC or 230 VAC
115/230 VAC power
supply
4.2.4 ).