Installation and electrical wiring
4.2.7.
Electrical wiring of a 8025 compact and a 8035,
115/230 VAC, without relays, with cable glands
Seal the unused cable gland using the stopper supplied to make sure the
device is tight.
→
Unscrew the cable gland nut.
→
Insert the stopper
→
Screw the nut back.
Only configure the selectors by unpowered device.
→
Lift the transparent lid after having unfastened the screw.
→
Unscrew the 4 screws then remove the cover from the device.
→
Insert the cable clips (see chap.
→
Pass the cables through the cable glands
→
Connect terminals according to pin assignment described below.
black wire* L-
4-20 mA output
red wire* L+
Jumper wire to
be removed if the
4-20 mA output is
connected
* factory wired
Fig. 26 :
Pin assignment of a 115/230 VAC version, without relays, with cable glands
4.2.3 ).
Pulse output "minus"
Pulse output "plus"
green/yellow wire*
PE
Cable to the flow
Connection of
rate sensor
115/230 VAC
power supply
E-28-
Flow transmitter 8025/8035
Switch to select either 115 VAC or
230 VAC
see chap. 3.3.4
Fuse
Earth, internally connected to the
earth plug