Installationandwiring
7.3.3.

connecting the pulse output

The pulse output is connected in NPN mode (default setting on a
version without current output) or in PNP mode (default setting on a
version with current output).
Load
white
2
brown
5
1
3
grey
4
blue
-
+
12-36 VDC
npn connection
Type 8081
Load
white
2
brown
5
1
3
grey
4
blue
-
12-36 VDC
pnp connection
7.3.4.

only connecting the current output

The current output, where present, is connected in source mode
(default setting) or in sink mode (on request).
4-20 mA
input
-
+
2
3
+
blue
Source mode connection
(default setting)
(*) If a direct earthing connection is not possible, fit a 100 nF/50 V capaci-
tor between the negative terminal of the power supply and the earth.
4-20 mA
input
-
+
brown
5
1
grey
4
black
(*)
-
+
Supply
12-36 VDC
Sink mode connection
(on request)
english
2
brown
5
1
3
4
grey
blue
(*)
-
+
Supply
12-36 VDC