Maintenance

6.
MAINTENANCE
6.1.

Maintening the device

If installation has been carried out properly and the operating conditions are correct, the
device is maintenance free.. Nevertheless if contamination or clogging occurs, clean the
wetted parts (paddle-wheel, axis, bearings) with water or any PVDF compatible cleaning
agent.
6.2.

If you encounter problems

Message
Meaning
displayed
ERROR 3
Memory read error: The user
settings are lost.
ERROR 4
Memory read error: the
totalizer values are lost.
ERROR 5
Memory read error: the user
settings and the totalizer
values are lost.
ERROR 6
Memory read error: the
totalizer values are lost.
ERROR 7
Memory read error: the user
settings and the totalizer
values are lost.
Flow transmitter 8025/8035
What to do
Switch the device off.
Switch the device on.
If the message is still displayed, press the
ENTER key to acknowledge the error: the
device operates with the default settings.
Adjust the device again.
If the message appears frequently, send the
device back to your reseller.
Press the ENTER key to acknowledge the
error: The values of the totalizers are set to
those of the last start of the device.
Check the values of the totalizers.
Press the ENTER key to acknowledge the
error: the device operates with the default
settings and the values of the totalizers are
set to those of the last start of the device.
Adjust the device again.
Check the values of the totalizers.
If the message appears frequently, send the
device back to your reseller.
Press the ENTER key to acknowledge the
error: the totalizers are reset.
Press the ENTER key to acknowledge the
error: the totalizers are reset.
Send the device back to your supplier.