Out (Output) - Setting The Output Signal - Burkert 8022 Mode D'emploi

Masquer les pouces Voir aussi pour 8022:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Type 8022
SettingandFunctions
9.4.3.
Out (Output) – setting the output signal
In this parameter, define whether the device is to work as a flow transmitter or a pulse divider.
setting as flow transmitter (4 - 20 mA):
When changing the unit (e.g. from liters to gallons) the limit values for the current output are not con-
verted automatically
Set the lower and upper limit values for the flow rate range associated to the 4-20 mA output, in the unit set
within the UNIT parameter.
The lower limit value is marked by an L (low) on the display and the upper limit value by an H (high).
setting as pulse divider (Freq):
noTE
as soon as the Freq parameter has been accessed, the output used (current output or frequency
output) is frozen to the last measured process value until the new k-factor has been validated.
• Validate the parameter as soon as the K factor is set.
Set the pulse dividing K factor in pulses/liter.
English
21

Publicité

Table des Matières
loading

Table des Matières