Adjustment and functions
5.2.
Read mode
The following parameters are displayed in the Read mode:
45,6 L/ m
16,45 mA
80529 L
6247 L .
5.3.
Settings mode
→
Simultaneously press keys
This mode makes it possible to:
LANGUAGE
UNIT
K-FACTOR
CURRENT
PULSE
RELAY
FILTER
TOTAL
END
Measured flow rate, in the chosen unit (see Settings mode).
4-20 mA output current value, proportional to the flow rate and
depending on the associated flow rate range.
Main totalizer in the chosen unit (see Settings mode). Reset
within the Settings mode.
Daily totalizer, in the same unit as the main totalizer. A decimal
point displayed after the unit differentiates this totalizer from the
main one. It may be reset by simultaneously pressing keys
for 2 s.
ENTER
for 5 seconds to access this mode.
Choose the display language (German, English, French or Italian).
Choose the unit the flow rate and the totalizers are displayed in.
Enter the K factor or determine it using the "Teach in" function.
Choose the flow rate range corresponding tothe 4-20 mA output
current.
Configuring the pulse output (unit and volume).
Configuring the relays. This function only appears on devices with
relays.
Choose the filter to dampen the fluctuations of the displayed
values and the current output. Ten dampening levels are available.
Reset both totalizers simultaneously.
Go back to the Read mode by saving the new settings.
E-40-
Flow transmitter 8025/8035
0......9