Electrical Wiring Of A 8025 Compact And A 8035, 115/230 Vac, With Relays, With Cable Glands - Burkert 8025 Manuel Utilisateur

Transmetteur de débit
Masquer les pouces Voir aussi pour 8025:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and electrical wiring
4.2.8.
Electrical wiring of a 8025 compact and a 8035,
115/230 VAC, with relays, with cable glands
Seal the unused cable gland using the stopper supplied to make sure the
device is tight.
Unscrew the cable gland nut.
Insert the stopper
Screw the nut back.
Only configure the selectors by unpowered device.
Lift the transparent lid after having unfastened the screw.
Unscrew the 4 screws then remove the cover from the device.
Insert the cable clips (see chap.
Pass the cables through the cable glands
Connect terminals according to pin assignment described below.
black wire* L-
red wire* L+
4-20 mA output
Selector [1] (see
Fig. 23 )
Jumper wire to
be removed if the
4-20 mA output is
connected
Connection relay
2 (see ex. Fig.
23 )
* factory wired
Fig. 29 :
Pin assignment of a 115/230 VAC version, with relays, with cable glands
The 4-20 mA current output of a transmitter with relays can be connected in either sourcing
or sinking mode to a 4-20 mA input. Depending on the connection mode, set the selector
[1] on "SOURCE" (sourcing mode) or on "SINK" (sinking mode).
4.2.3 ).
Pulse output "minus"
Pulse output "plus"
green/yellow
wire* PE
see chap. 3.3.4
Connection of 115/230 VAC power supply
Cable to the flow rate sensor
Connection relay 1 (see
ex. Fig. 23 )
Relay cables must be fitted here to the board using the
supplied cable clips (see chap. 4.2.3 )
E-30-
Flow transmitter 8025/8035
Switch to select either
115 VAC or 230 VAC
Fuse
Earth, internally connected to the
earth plug

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

8035

Table des Matières