Installation
Maximum Line Set Distance Formula
Step 1.
Measured Rise (R) 35 feet (10.7 meters)
Maximum
_____ x 1.7 =
_____ Calculated Rise
Step 2.
Measured Drop (D) 15 feet (4.5 meters)
Maximum
_____ x 6.6 =
_____ Calculated Drop
Step 3.
Measured Horizontal Distance (H) 100 feet
(30 meters) Maximum
_____ Horizontal Distance
Step 4.
Total Calculated Distance 150 feet
(45 meters) Maximum
_____ Total Calculated

Notice
The refrigeration system warranty will
not apply if the Manitowoc Ice Machine
and Manitowoc CVD Condensing Unit are
not installed according to specifications.
This warranty also will not apply if the
refrigeration system is modified with a
condenser, heat reclaim device, or other
parts or assemblies not approved by
Manitowoc.
24
Distance
QuietQube® Models with CVD
Step 1 Secure the Condensing Unit
Through‑holes are provided to secure the
condensing unit to a curb, rack or wooden
timber.
Step 2 Route the Refrigeration Tubing
Route the refrigeration tubing between
the ice machine head section and the
condenser or CVD condensing unit.
• A suction line oil trap is required when
rise is more than 20 feet (6 meters).
• Only one trap is allowed in the line set.
• Shorten the line set as required, do not
coil line set.
Part Number 000017556 Rev 00 9/22