Installation
Condensing Unit Installation
Each ice machine head section ships
from the factory with a refrigerant
charge appropriate for the entire system
operation. The serial tag on the ice machine
indicates the refrigerant charge.
QuietQube
Condensing
Ice Machine
SF3000C
CVDF3000
*All line sets must be insulated with Armaflex

Notice
Manitowoc systems are only approved and
warranted as a complete new package.
Warranty on the refrigeration system will
be void if a new ice machine head section
is connected to preexisting (used) tubing
or condensing units or vice versa.
,
The refrigeration system warranty will
not apply if the Manitowoc Ice Machine
and Manitowoc CVD Condensing Unit are
not installed according to specifications.
This warranty also will not apply if the
refrigeration system is modified with a
condenser, heat reclaim device, or other
parts or assemblies not manufactured by
Manitowoc.
22
Line Set
Unit
RC‑24
RC‑34
RC‑54
Caution
Installation of a QuietQube® Condensing
Unit may require the use of special
equipment for placement. Trained and
qualified personnel are required for proper
rigging and lifting. Holes are provided
on the corners of the condensing unit to
allow the use of lifting shackles.
Suction Line
Liquid Line
Two Lines
One Line
0.75"
0.625"
(19 mm)
(16 mm)
Part Number 000017556 Rev 00 9/22
Warning
n
Minimum
Insulation
Thickness
0.75" (19 mm)
Suction Line
0.25"(7 mm)
Liquid Line
Section 2