Section 2
Water Connections
• Local water conditions may require
treatment of the water to inhibit scale
formation, filter sediment, and remove
chlorine odor and taste.
• Follow these guidelines to install water
inlet lines:
• Plumbing must conform to local codes.
• Do not connect the ice machine to a
hot water supply. Be sure all hot water
restrictors installed for other equipment
are working. (Check valves on sink
faucets, dishwashers, etc.)
• ST3000W ‑ are equipped with a High
Pressure Valve rated for water pressure
from 20 psi to 350 psi (1.37 bar to
24.1 bar).
• SF3000C ‑ If water pressure exceeds
the maximum recommended pressure
of 80 psig (1.5 bar), obtain a water
pressure regulator from your Manitowoc
distributor.
• Install a water shut‑off valve and union
for potable water and water cooled
condenser lines.
• Insulate water inlet lines to prevent
condensation.
,
Do not apply heat to water inlet valve or
water drain fittings. Heating will damage
the nonmetallic connector. Do not over
tighten fittings. Two turns after hand tight
is the maximum.
n
Connect to a potable water supply only
Part Number 000017556 Rev 00 9/22
Caution
Warning
Water-Cooled Condenser Water Pressure
ST300W ‑ Water pressure at the condenser
cannot exceed 350 psi (24.1 bar).
Cooling Tower Applications
(Water-Cooled Models)
A water cooling tower installation does not
require modification of the ice machine.
The water regulator valve for the condenser
continues to control the refrigeration
discharge pressure.
• Water entering the condenser must not
exceed 90°F (32.2°C).
• Water flow through the condenser
must not exceed 5 gallons (19 liters) per
minute.
• Allow for a pressure drop of 7 psi
(0.5 bar) between the condenser water
inlet and the outlet of the ice machine.
• Water exiting the condenser must not
exceed 110°F (43.3°C).

Important
The Commonwealth of Massachusetts
requires that all water‑cooled models
must be connected only to a closed loop,
cooling tower system.