Location Requirements
The location selected for the ice machine
head section must meet the following
criteria. If any of these criteria are not met,
select another location.
• The location must be indoors, and free of
airborne and other contaminants.
• The location must not be near
heat‑generating equipment or in direct
sunlight and must be protected from
weather.
• The location must allow enough
clearance for water, drain, and electrical
connections in the rear of the ice
machine
• The location must not obstruct air flow
through or around the ice machine.
Refer to the chart for clearance
requirements.
• The location must be capable of
supporting the weight of the ice
machine, bin and a full bin of ice.
• Local water conditions may require
treatment of the water to inhibit scale
formation, filter sediment, and remove
chlorine odor and taste.
• The ice machine and bin must be level.
Part Number 000017556 Rev 00 9/22
Section 2
Installation
Installation Requirements
Head Sections
• Vent the ice machine and bin drains
separately.
• The ice machine and bin must be
de‑scaled and sanitized after installation.
• The drain line must contain a union or
other suitable means of disconnection at
the ice machine.
QuietQube® Models Only
• The ice machine top panel can be
trimmed with an aviator snips to allow
the line set, water line and electrical
connections to exit the top. Only cut out
what is needed, the back panel must
support the top panel.
• The water inlet and electrical connection
must contain a service loop to allow
future access.
Condensing Unit (CVD)
• The location must not allow exhaust
fan heat and/or grease to enter the
condenser.
• The location must not obstruct airflow
through or around the condensing unit.
13