Télécharger Imprimer la page

elsner elektronik WS1 Installation Et Commande page 126

Commande pour jardin d'hiver
Masquer les pouces Voir aussi pour WS1:

Publicité

Les langues disponibles

Les langues disponibles

Power consumption
Internal hygrometer
Internal thermometer
The following standards were referenced with regard to evaluating electro-
magnetic compatibility of the product (Interference emission/ Interference
immunity):
EN 60730-1:2000-11 + A11:2002
The product has been tested by an accredited EMC laboratory according to the
abovementioned standards.
Weather station
Housing
Colour
Mounting
Protection category
Dimensions
Weight
Ambient temperature
Operating voltage
Current
Power consumption
Heating rain sensor
Temperature sensor
Wind sensor
Sun sensor
max. 15 W, Stand-by approx. 8 W
Measurement
1...99% RH
range
Resolution
1% RH
Measurement
0...+50°C
range
Plastic material
White / translucent
On-wall
IP 44
approx. 96 x 77 x 118 (W x H x D, mm)
approx. 160 g
Operation -30...+50°C, storage -30...+70°C
24 V DC
max. 120 mA
max. 3.6 W, Stand-by approx. 2 W
approx. 1.2 W
Measurement
-40...+80 °C
range
Resolution
0.1°C
Accuracy
±0,5°C at +10...+50°C
±1,5°C at -25...+80°C
Measurement
0 m/s to 70 m/s
range
Resolution
<10% of the measured value
Accuracy
±25% at 0...15 m/s
at an angle of incidence of 45°,
pole-mounting
Measurement
0 to 99.000 lux
range
Resolution
1 lux at 0...120 lux
2 lux at 121...1 046 lux
63 lux at 1 047...52 363 lux
423 lux at 52 364...99 000 lux
Accuracy
±35%
125