Version With The Current Output - Burkert 8311 Manuel D'installation

Masquer les pouces Voir aussi pour 8311:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4.3.3 Version with the current output

V+
V+
0 V
0 V
A
4-20 ma current output
8311
PNP, default; To change the configuration from PNP to NPN, do the following:
1)
- unplug the M12 power supply connector
- unscrew the 4 wires of the transmitter cover
- change the position of the 2 straps (attention: if one output is configured as an nPn
output and the other as a PnP output, the 4-20 ma output is no more utilisable)
PnP configuration
- Replace the cover in its initial orientation then tighten the 4 screws in an alternating pattern
- plug connector M12 back
V+
V+
A
or
0 V
0 V
(*)
(*)
operating safety
Always check the wiring of the cable plugs to ensure the good operating
of the device.
nPn configuration
V+
1
(12-30 VDC)
3
0V
Wiring of en 175301-803 fixed connector
1
Not connected
2

Publicité

Table des Matières