Maintenanceandtroubleshooting
status of
problem
the bar
status red led
graph
The device
Off
Flashes twice
does not
briefly every 5
respond
seconds
The device
Off
Off
does not
work
Flow meas-
-
Off
urement
incorrect
All the
Off
LEDs are
on
Type 8041
status
status green
current or
led
frequency
output
Flashes once
22 mA and
per second
0 Hz
Off
0 mA and
0 Hz
-
Flashes
0 mA and
irregularly or
0 Hz
goes off
Off
0 mA and
0 Hz
Flashes once
-
per second
Flashes once
20 mA and
per second
240 Hz
meaning / causes
What to do
Calibration of the full
scale has failed because
fluid velocity > 10 m/s.
The device is unplugged.
The fuse in the installation
is in poor condition.
The switch on the instal-
lation is on the OFF
position.
The power supply is
incorrectly connected to
the + and - terminals.
The power supply is not
stabilised.
The device is out of order.
The K factor has been
incorrectly calculated.
Measurement range
exceeded by less than
20%
English
Clear the error by briefly pressing the
push button.
Check the fluid velocity.
Restart calibration of the full scale
(see § 10.8).
Plug in the device.
Change the fuse.
Turn the switch on the installation to
ON.
Check the wiring (see §
8.3.1, 8.3.2
and 8.3.3).
Change the power supply.
Return the device to your Bürkert
retailer.
Recalculate the K factor (see §
Select the higher measurement range
(see § 10.6)
6.3.5).
49