11.5.1.
problems signalled by the leds
status of
problem
the bar
status red led
graph
The device
Off
Flashes once
does not
briefly every 2
respond
seconds
The device
Off
Flashes twice
does not
briefly every 2
respond
seconds
The device
Off
Flashes twice
does not
briefly every 3
respond
seconds
The device
Off
Flashes twice
does not
briefly every 4
respond
seconds
48
status
status green
current or
led
frequency
output
Flashes once
22 mA and
per second
256 Hz
Flashes once
22 mA and
per second
0 Hz
Flashes once
22 mA and
per second
0 Hz
Flashes once
22 mA and
per second
0 Hz
English
Type 8041
Maintenanceandtroubleshooting
meaning / causes
What to do
→
Measurement range
exceeded by more than
→
20%
→
Calibration of the "zero
flow" point has failed.
→
→
→
→
The device is out of order.
→
Calibration of the full
scale has failed because
→
fluid velocity < 2 m/s.
→
Clear the error by briefly pressing the
push button.
Consult the graphs (see §
8.2.1).
Clear the error by briefly pressing the
push button.
Check upstream/downstream dis-
tances (see § 8.2.1).
10.7).
Restart calibration (see §
If the error persists, contact your
Bürkert retailer.
Contact your Bürkert retailer.
Clear the error by briefly pressing the
push button.
Check the fluid velocity.
Restart calibration of the full scale
(see § 10.8).