Select the measurement
range using switches 4 and 5,
see § 10.6.
→
Install the device in the
pipe.
→
Thread the cables through
the cable glands and make the
connections to the electronic
board, see § 8.3.
→
Connect the shield on the
power cable to the earth § 8.3.
→
Fill the pipe.
→
Switch on the device.
→
Calibrate the "zero flow"
point, see § 10.7.
14
English
Type 8041
QuickInstallation
Calibrate the
full scale of the
measurement
range?
Yes
→
Calibrate the full scale,
see § 10.8.
No
Are the 10 LEDs on
the bargraph on?
Yes
→
Set the relay output param-
eters, see § 10.9
No
→
Check
that the fluid
velocity > 2 m/s
and < 10 m/s.