Installationandwiring
7.3.

electrical wiring

danger
Risk of injury due to electrical voltage
Before starting work, make sure that you switch off the supply
voltage and secure it to prevent restarting.
Do not unscrew the cover of a powered device.
Observe all applicable accident protection and safety guidelines
for electrical equipment.
to ensure that the device runs correctly, plug in and
tighten the connectors.
protect the electrical power supply and the relay
Fit the power supply with a 1A fuse if it is not protected
by default.
Protect the relay with fuse of 3A max. and a circuit
breaker.
noTe
Use a shielded cable with an operating temperature limit
> +80°C (+176°F).
Use a high quality electrical power supply, filtered and
regulated.
Type 8400
7.3.1.

Assembling the connectors

Unscrew the nut [1] on the cable gland.
2
Remove the screw terminal block [3] from the
housing [2].
3
Insert the cable into the nut [1] and then the
seal [4], into the cable gland and finally through
4
the housing [2].
Make the connections to the screw terminal
1
block [3] (see chap. 7.3.3).
Position the terminal block [3] in steps of 90°
and then put it back into the housing [2], pulling
gently on the cable so that the wires do not
clutter the housing.
Tighten the nut [1] on the cable gland.
Place the seal [5] between the connector and
the EN175301-803 fixed connector on the
device and then insert the 2508 connector into
5
the fixed connector.
Insert and then tighten the screw [6] to ensure
6
correct tightness and electrical contact.
Fig. 7:
Assembling the 2508 type female connector (provided)
Unscrew the nut [1] on the body [4].
4
3
2
1
Insert the cable into the nut [1], the cable
clamp [2] and the seal [3], and then into
the body [4].
english