Electrical Wiring - Burkert 8222 ELEMENT neutrino Manuel Utilisateur

Transmetteur de conductivité
Masquer les pouces Voir aussi pour 8222 ELEMENT neutrino:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

8.3.

Electrical wiring

danger
Risk of injury due to electrical voltage
Before starting work, make sure that you switch off the supply
voltage and secure it to prevent restarting.
Observe all applicable accident protection and safety guidelines
for electrical equipment.
use a high quality electrical power supply (filtered
and regulated).
make sure the installation is equipotential.
8.3.1.
Wiring a version with cable gland
Select a cable that meets the specifications detailed in chapter
6.3.6.Electrical connections.
Fig. 14:
Stripping the cable and exposing the wires.
24
All manuals and user guides at all-guides.com
Strip 75 to 85 mm of the cable.
Expose 8 to 9 mm of wire on
the stripped cable.
Type 8222 ELEMENT neutrino
Installationandwiring
A
B
Fig. 15:
Threading the cable into the cable gland.
Tighten the cable gland.
Connect the 4-20 mA output (see
english
Unscrew and remove
the cable gland nut [A].
Remove the stopper [B]
from the cable gland.
Unscrew the cover on
the connection box (see
§ 7.2)
Thread the cable
through the cable gland
nut and the cable gland.
Pull the cable into the
box until the end of the
stripped part of the
cable sticks out of the
cable gland by 5-6 mm.
Roll a cable clamp
around the cable sheath
(twice).
Tighten the cable clamp.
Pull the cable out of the
box to check that it is
secure.
Fig. 16).

Publicité

Table des Matières
loading