3 INSTALLATION
8025
2
Position A
1
3
Fig. 3.9 PLC-connection
3.4.3 Connection of Pulse Output to a PLC
The pulse output (8025 with or without relay) can easily be connected to a PLC,
independently of the respective version (see fig. 3.10).
8025
6
5
Fig. 3.10 Connection of pulse output to a PLC
3.4.4 Electrical Wiring with Power Supply 230/115 VAC (option)
Remove the cover of the device, the powersupply board is in the bottom of the housing.
Pull cable through PG 13,5 and wire according to fig. 3.11.
The connection of the output signals (current, pulse and relays) are not affected.
If the current output 4...20 mA is used, remove the straps.
8025 - 8025RR
V+
L+
PLC
4...20 mA
L-
0V
V+
Puls+
PLC
Puls-
0V
FLOW TRANSMITTER 8025
8025
Position B
8025
Puls+
6
Puls-
5
E-15-
V+
2
L+
4...20 mA
1
PLC
3
L-
0V
V+
PLC
0V