Code
Possible settings
No.
Name
Lenze
C0014
Operating mode
2
v
C0015
V/f rated
50.00 7.50
frequency
uSEr
à
C0016
U
boost
min
uSEr
C0034*
Setpoint
selection range
v
Standard–I/O
0
(X3/8)
uSEr
−34−
L
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
The most important codes for commissioning
Selection
2
V/f characteristic control V ~ f
(Linear characteristic with constant V
boost)
2
3
V/f characteristic control V ~ f
(Square−law characteristic with constant
V
boost)
min
4
Vector control
5
Sensorless torque control with speed
limitation
l
Torque setpoint via C0412/6
l
Speed limitation via setpoint 1
(NSET1−N1), if C0412/1 is assigned, if
not via max. frequency (C0011)
{0.02 Hz}
0.00
{0.01 %}
0
Unipolar voltage 0 ... 5 V / 0 ... 10 V
Current 0 ... 20 mA
1
Current 4 ... 20 mA
2
Bipolar voltage −10 V ... +10 V
3
Current 4 ... 20 mA open−circuit monitored
EDK82EV113 DE/EN/FR 8.1
7
Commissioning
IMPORTANT
l
Commissioning without motor
parameter identification possible
min
l
Benefit of identification with
C0148:
– Improved smooth running at low
speed
– V/f rated frequency (C0015) and
slip (C0021) are calculated and
stored. They do not have to be
entered
For initial selection enter the motor
data and identify the motor
parameters with C0148
Otherwise commissioning is not
possible
960.00
l
C0015 is calculated and stored
under C0148 when the motor
parameters are identified
Settings applies to all possible
l
mains voltages
40.00
à
Depending on the controller
Setting applies to all mains voltages
permitted
Observe the switch position of the
function module!
Changing the direction of rotation is
only possible with a digital signal.
Minimum output frequency (C0010)
l
not effective
l
Individual adjustment of offset and
gain
TRIP Sd5, if I < 4 mA
Changing the direction of rotation is
only possible with a digital signal.
147