7
Commissioning
Using the keypad E82ZBC − Vector control
Switch−on sequence
12.
Activate the control mode "vector control"
(C0014 = 4)
Lenze setting: Linear V/f characterisitic control
(C0014 = 2)
13.
Adapt the voltage/current range to the analog
setpoint (C0034)
Lenze setting: 0, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)
14.
Enter the motor data
A
Rated motor speed (C0087)
Lenze setting: 1390 rpm
B
Rated motor current (C0088)
Lenze setting: Depending on the controller
C
Rated motor frequency (C0089)
Lenze setting: 50 Hz
D
Rated motor voltage (C0090)
Lenze setting: Depending on the controller
E
Motor−cosj (C0091)
Lenze setting: Depending on the controller
15.
Start the motor paramter identification (C0148)
A
Ensure that the controller is inhibited
B
Set C0148 = 1
C
Enable the controller.
D
If the segment becomes active after approx. 30
c
s,
inhibit the controller once again
126
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Note
1
PS
001 4
000
2
Hi
Lo
Set the DIP switch on the
1
PS
0034
000
standard−I/O to the same range (see
0
Hi
Mounting Instructions for the
Lo
standard−I/O)
See motor nameplate
Enter the value for the motor
connection type (star/delta) selected!
Enter the value for the motor
connection type (star/delta) selected!
Only when the motor is cold!
1
PS
01 48
000
0
Hi
Lo
X3
Terminal X3/28 = LOW
20
28
misc001
v
Press
in addition
X3
l
Terminal X3/28 = HIGH
20
28
misc002
l
The identification starts:
– The segment
– The motor makes a
X3
Terminal X3/28 = LOW
l
20
28
Identification is completed.
l
misc001
Calculated and stored:
l
– V/f rated frequency (C0015)
– Slip compensation (C0021)
– Motor stator inductance
Measured and stored:
l
– Motor stator resistance
EDK82EV113 DE/EN/FR 8.1
c
Off
high−pitched tone. The motor
does not rotate!
(C0092)
(C0084) = Total resistance of
motor cable and motor
L