3
Electrical installation
Mains connection 400 V/500 V
Fuses and cable cross−sections (operation with increased rated power)
8200 vector
mains
Type
[kW]
E82EV302K4C
3.0
3/PE AC
E82EV402K4C
4.0
320 ... 440 V;
45 ... 65 Hz
E82EV752K4C
7.5
8200 vector
mains
Type
[kW]
E82EV302K4C
3.0
3/PE AC
E82EV402K4C
4.0
320 ... 440 V;
45 ... 65 Hz
E82EV752K4C
7.5
Fuse
E.l.c.b.
1)
Use UL−approved cables, fuses and fuse holders only.
UL fuse: Voltage 500 ... 600 V, tripping characteristic "H", "K5" or "CC"
2)
All−current sensitive e.l.c.b. for use with E82EVxxxK4C0xx
3)
All−current sensitive e.l.c.b. for use with E82EVxxxK4C2xx
Observe national and regional regulations (e. g. VDE 0113, EN 60204)
Please observe the following when using e.l.c.bs:
E.l.c.bs must only be installed between mains supply and controller.
l
E.l.c.bs can trip incorrectly because of
l
– capacitive leakage currents of the cable shields during operation (especially with
long, shielded motor cables),
– simultaneous connection of several controllers to the mains supply,
– use of additional RFI filters.
104
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Operation without mains choke
Installation to EN 60204−1
Installation to UL
L1, L2, L3,
PE
2
[mm
]
M16 A
B16 A
2.5
15 A
Operation only with mains choke
Operation only with mains choke
Operating with mains choke
Installation to EN 60204−1
Installation to UL
L1, L2, L3,
PE
2
[mm
]
M10 A
B10 A
1.5
10 A
M16 A
B16 A
2.5
15 A
M25 A
B25 A
4
25 A
EDK82EV113 DE/EN/FR 8.1
1)
L1, L2, L3,
FI
PE
[AWG]
14
³ 300 mA
2)
³ 30 mA
3)
1)
L1, L2, L3,
FI
PE
[AWG]
16
³ 300 mA
2)
14
³ 30 mA
3)
10
L