Télécharger Imprimer la page

Lenze 8200 Vector Instructions De Montage page 144

Masquer les pouces Voir aussi pour 8200 Vector:

Publicité

Les langues disponibles

Les langues disponibles

Code
Possible settings
No.
Name
Lenze
C0002*
Saving of own
s
settings
uSEr
(cont.)
C0002*
Loading/copying
s
of your own
basic settings
uSEr
(cont.)
C0003*
Non−volatile
1
v
parameter
saving
L
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
The most important codes for commissioning
Selection
ð
9
PAR1
Own settings
ð
5
Own settings
PAR1
ð
6
Own settings
PAR2
ð
7
Own settings
PAR3
ð
8
Own settings
PAR4
0
Parameter not saved in EEPROM
1
Parameter always saved in EEPROM
3
Own settings saved in EEPROM
EDK82EV113 DE/EN/FR 8.1
7
Commissioning
IMPORTANT
You can save your own basic settings
for a controller (e.g. machine delivery
status):
1. Ensure that parameter set 1 is
active
2. Controller inhibit
3. Set C0003 = 3, acknowledge with
v
4. Set C0002 = 9, acknowledge with
v
, to save your own basic
settings
5. Set C0003 = 1, acknowledge with
v
6. Enable the controller.
Using this function, PAR1 can be
copied to parameter sets PAR2 ...
PAR4
Restorage of own basic setting in the
selected parameter set
Data loss after mains disconnection
l
Active after every mains
connection
l
Cyclic parameter changes via bus
module are not allowed.
Subsequently save parameter set 1 as
own basic setting with C0002 = 9
143