Montageanleitung
Mounting Instructions
Instructions de montage
8200 vector
0.25 kW ... 2.2 kW

Publicité

Table des Matières
loading

Sommaire des Matières pour Lenze 8200 vector

  • Page 1 Show/Hide Bookmarks EDK82EV222 !KX/ Montageanleitung Mounting Instructions Instructions de montage 8200 vector 0.25 kW ... 2.2 kW...
  • Page 2 Die Betriebsanleitung mit ausführlicher Information zum Frequenzumrichter 8200 vector können Sie bei Ihrem Lenze-Vertriebspartner bestellen. Detailed Operating Instructions for the 8200 vector can be ordered directly from Lenze or Lenze representatives. Les instructions de mise en service comprenant une description complète du convertisseur de fréquence 8200 vector peuvent être commandées auprès de votre agence Lenze.
  • Page 3 Show/Hide Bookmarks L1 / L2 / L3 / N / PE K14 K11 K12 8200vec014 The device has no overspeed protection. Must be provided with external or remote overload protection. Suitable for use on a circuit capable of delivering not more than 5000 rms symmetrical Warnings! amperes, 240 V maximum (240 V devices) or 500 V maximum (400/500 V devices) resp.
  • Page 4 (Auslieferungszustand). – Ohne die FIF-Abdeckkappe ist der 8200 vector gesperrt (Keypad: Da der 8200 vector ohne Funktionsmodul keine Steuerklemmen hat, kann Starten und Stoppen während des Betriebs auch über Netzschalten erfolgen. – Bei zyklischen Schaltvorgängen: Pausenzeit von 3 Minuten beachten!
  • Page 5: Table Des Matières

    Show/Hide Bookmarks Inhalt Sicherheitshinweise ........Lieferumfang .
  • Page 6: Sicherheitshinweise

    Allgemeine Sicherheits- und Anwendungshinweise für Lenze-Antriebsregler (gemäß Niederspannungsrichtlinie 73/23/EWG) 1. Allgemein Lenze-Antriebsregler (Frequenzumrichter, Servo-Umrichter, Stromrichter) können während des Betriebs - ihrer Schutzart entsprechend - spannungsführende, auch bewegliche oder rotierende Teile haben. Oberflächen können heiß sein. Bei unzulässigem Entfernen der erforderlichen Abdeckung, bei unsachgemäßem Einsatz, bei falscher Installation oder Bedienung besteht die Gefahr von schweren Personen- oder Sachschäden.
  • Page 7 UL-Anlagen gelten. Die Dokumentation enthält spezielle Hinweise zu UL. 7. Sicherer Halt Die Variante V004 der Antriebsregler 9300 und 9300 vector und die Variante Bx4x der Antriebsregler 8200 vector unterstützt die Funktion ”Sicherer Halt”, Schutz gegen unerwarteten Anlauf, nach den Anforderungen von Anhang I Nr.
  • Page 8 Show/Hide Bookmarks Sicherheitshinweise Restgefahren Perso- Überprüfen Sie vor Arbeiten am Antriebsregler, ob alle Leistungsklemmen, der Relaisausgang nen- und die Pins der Schnittstelle FIF spannungslos sind, da schutz – nach dem Netzabschalten die Leistungsklemmen U, V, W, +UG, -UG, BR1, BR2 und die Pins der Schnittstelle FIF noch mindestens 3 Minuten gefährliche Spannung führen.
  • Page 9: Gestaltung Der Sicherheitshinweise

    Show/Hide Bookmarks Sicherheitshinweise Gestaltung der Sicherheitshinweise Alle Sicherheitshinweise in dieser Anleitung sind einheitlich aufgebaut: (kennzeichnet die Schwere der Gefahr) Signalwort Hinweistext (beschreibt die Gefahr, gibt Hinweise, wie sie vermieden werden kann) verwendete Piktogramme Signalwörter Warnung vor Gefahr! Warnt vor unmittelbar drohender Gefahr. Warnung vor gefährlicher Personen-...
  • Page 10: Lieferumfang

    X1.1 X1.2 X2.1 X2.2 Æ 5 mm Æ 8 mm Æ 10 mm 8200vec002 Frequenzumrichter 8200 vector Montageanleitung ¶ 15 bzw. ¶ 17 Klemmleiste X1.1: Netzanschluß, DC-Einspeisung ¶ 19 Klemmleiste X1.2: Relaisausgang Klemmleiste X2.1: Motoranschluß, Anschluß Bremswiderstand (Option) ¶ 18 ¶...
  • Page 11: Technische Daten

    Show/Hide Bookmarks Technische Daten Konformität Niederspannungsrichtlinie (73/23/EWG) Approbationen UL 508C Underwriter Laboratories (File-No. E132659) Power Conversion Equipment ab Gerätestand E82EVxxxKxBxxxXX 1F 14 Max. zulässige Motorleitungslänge Max. zulässige Motorleitungslänge Bei Netz-Bemessungsspannung Bei Netz Bemessungsspannung geschirmt: 50 m und Schaltfrequenz 8 kHz (ohne zusätzliche Ausgangsdrosseln) ungeschirmt: 100 m...
  • Page 12 Show/Hide Bookmarks Technische Daten Leistung Leistung Netzspannung Netzspannung Netzstrom Netzstrom Ausgangsstrom wicht (60 s) E82EV251K2B 0.25 kW 3.4 A 1.7 A 2.6 A 0 8 kg 0.8 kg E82EV371K2B 0.37 kW 1/N/PE AC 230/240 V 5.0 A 2.4 A 3.6 A 1/N/PE AC 230/240 V E82EV551K2B 0.55 kW...
  • Page 13: Mechanische Installation

    Show/Hide Bookmarks Mechanische Installation Abmessungen bei Standard-Befestigung Abb. 1-1 4 Nm 35 lbin 8200vec004 Maße in mm Maße in mm E82EV251K2B 180 210 130...140 120...170 110...200 120 E82EV371K2B 6 5 27 5 6.5 27.5 E82EV551KxB 240 270 190...200 180...230 170...260 180 E82EV751KxB E82EV152KxB 250...260...
  • Page 14: Elektrische Installation

    Show/Hide Bookmarks Elektrische Installation EMV-gerechte Installation Abb. 1-2 8200vec008 Stop! Steuerleitungen und Netzleitungen räumlich getrennt von der Motorleitung verlegen, um Störeinkopplungen zu vermeiden. Funktionsmodul (Option) Stern- oder Dreieckschaltung wie auf dem Motor-Typenschild angegeben EMV-Kabelverschraubung (nicht im Lieferumfang enthalten) geschirmte Motorleitung, kapazitätsarm (Ader/Ader ≤ 75 pF/m; Ader/Schirm ≤ 150 pF/m) Leitungsschirm großflächig auf PE-Potential legen (PES).
  • Page 15 Show/Hide Bookmarks Elektrische Installation EMV-gerechte Installation Einhaltung der Anforderungen nach EN 61800-3/A11 Störaussendung Störaussendung Einhaltung der Grenzwertklassen A und B nach EN 55011 E82EVxxxKxB00x ohne zusätzliche Maßnahmen E82EVxxxKxB20x nur mit externen Filtermaßnahmen Tip! Wenn Sie die Adern für den Motoranschluß und die Adern für den Anschluß des PTC oder Thermokontakts in einem Kabel mit gemeinsamem Schirm führen, müssen Sie zusätzlich einen Ferritkern Typ EZZ0013 installieren: –...
  • Page 16: Klemmleisten Verdrahten - Einfach Und Sicher

    Show/Hide Bookmarks Elektrische Installation Klemmleisten verdrahten - einfach und sicher Die mitgelieferten Klemmleisten sind geprüft nach den Spezifikationen der DIN VDE 0627:1986-06 (in Teilen) DIN EN 60999:1994-04 (in Teilen) Geprüft wurden u. a. mechanische, elektrische und thermische Beanspruchung, Vibration, Leiterbe- schädigung, Leiterlockerung, Korrosion und Alterung.
  • Page 17: Netzanschluß 230 V/240 V

    Show/Hide Bookmarks Elektrische Installation Netzanschluß 230 V/240 V Stop! Antriebsregler Typ E82EVxxxK2B nur an Netzspannung 1/N/PE AC 180 ... 264 V bzw. 3/PE AC 100 ... 264 V anschließen. Höhere Netzspannung zerstört den Antriebsregler! Der Ableitstrom gegen Erde (PE) ist > 3.5 mA. Nach EN 50178 ist eine Festinstallation erforderlich.
  • Page 18: Netzanschluß 230 V/240 V

    Show/Hide Bookmarks Elektrische Installation Netzanschluß 230 V/240 V Sicherungen und Leitungsquerschnitte Netz Netz Installation nach EN 60204-1 Installation nach UL Schmelzsi- Sicherungs- L1, L2, L3, N, PE Schmelzsi- L1, L2, L3, N, PE cherung automat cherung [AWG] M10 A C10 A 10 A E82EV251K2B E82EV371K2B 1/N/PE AC...
  • Page 19 Show/Hide Bookmarks Elektrische Installation Netzanschluß 400 V E82EV551K4B E82EV751K4B E82EV152K4B X1.1 E82EV222K4B X1.1 L3 PE +UG -UG L2/N Abb. 1-4 L1 L2 3/PE AC 400 V 8200vec011 X1.1/+UG, X1.1/-UG DC-Einspeisung (DC-Verbundbetrieb siehe Betriebsanleitung) Sicherungen und Leitungsquerschnitte Netz Netz Installation nach EN 60204-1 Installation nach UL Schmelzsi- Sicherungs-...
  • Page 20: Anschluß Motor / Bremswiderstand

    Kapazitätsarme Motorleitungen verwenden! (Ader/Ader ≤ 75 pF/m, Ader/Schirm ≤ 150 pF/m) Möglichst kurze Motorleitungen wirken sich positiv auf das Antriebsverhalten aus! HF-Schirmabschluß durch PE-Anbindung über Schirmschelle bzw. EMV-Kabelverschraubung X2.1/PE Ausgangsseitige Erdung des 8200 vector X2.1/BR1, Anschlußklemmen Bremswiderstand X2.1/BR2 (Informationen zum Betrieb mit Bremswiderstand: siehe Betriebsanleitung) X2.2/T1,...
  • Page 21: Anschluß Relaisausgang

    Anschluß Relaisausgang Abb. 1-6 8200vec013 Funktion Meldung Relaisstellung Technische Daten geschaltet (Lenze-Einstellung) X1.2/K11 Relaisausgang Öffner geöffnet TRIP AC 250 V/3 A AC 250 V/3 A X1.2/K12 Relais-Mittelkontakt DC 24 V/2 A DC 24 V/2 A ... DC 240 V/0.22 A DC 240 V/0 22 A X1.2/K14 Relaisausgang Schließer...
  • Page 22: Funktionsmodul (Option)

    Show/Hide Bookmarks Funktionsmodul (Option) Montage Gefahr! Die Pins der Schnittstelle FIF führen gefährliche Spannung! Montieren Sie das Funktionsmodul nur bei vom Netz getrenntem Antriebsregler. Warten Sie nach dem Trennen vom Netz mindestens 3 Minuten, bevor Sie mit den Arbeiten beginnen. 1.
  • Page 23: Demontage

    Show/Hide Bookmarks Funktionsmodul (Option) Demontage Demontieren Sie ein Funktionsmodul nur, wenn es unbedingt notwendig ist (z. B. beim Austausch des Antriebsreglers). Die Stiftleiste, auf die das Funktionsmodul aufgesteckt wird, ist Teil der Kontaktführung des Antriebs- reglers. Sie ist nicht ausgelegt für wiederholtes Aufstecken und Abnehmen des Funktionsmoduls! Gefahr! Die Pins der Schnittstelle FIF führen gefährliche Spannung! Demontieren Sie das Funktionsmodul nur bei vom Netz getrenntem Antriebsregler.
  • Page 24 Show/Hide Bookmarks Funktionsmodul (Option) Demontage 1. Antriebsregler vom Netz trennen und mindestens 3 Minuten warten! 2. Schraubendreher maximal 5 mm in die Öffnung oben am Funktionsmodul einführen. max. 5 mm! 3. Schraubendreher nach oben drücken und damit das Funk- tionsmodul ausrasten. So lange 3 min drücken, bis es “knackt”.
  • Page 25: Kommunikationsmodul (Option)

    Show/Hide Bookmarks Kommunikationsmodul (Option) Montage/Demontage Kommunikationsmodul auf die Schnitt- stelle AIF aufstecken bzw. davon abzie- hen. Das ist auch während des Betriebs mög- lich. 8200vec073 Spannungsversorgung extern Ab Gerätestand E82EVxxxKxBxxXX 1F 14 Spannungsversorgung über können Sie die Kommunikationsmodule interne Spannungsquelle (Lieferzustand) auch über die interne Spannungsquelle auch über die interne Spannungsquelle...
  • Page 26: Inbetriebnahme

    Show/Hide Bookmarks Inbetriebnahme Parametrieren mit dem Keypad Das Keypad ist als Zubehör erhältlich. Die vollständige Beschreibung des Keypad finden Sie im Falt- blatt, das jedem Keypad beiliegt. Funktionstasten Statusanzeigen Bargraph-Anzeige Funktionsleiste 1 Funktionsleiste 2 Parametersatz Änderung Änderung Codenummer möglich, möglich, wenn An- Subcodenummer zeige blinkt...
  • Page 27 Tip! Über C0002 ”Parametersatz-Transfer/Lieferzustand herstellen” können Sie bequem Konfi- gurationen von Antriebsregler zu Antriebsregler transferieren oder wieder den Lieferzu- stand herstellen, indem Sie die Lenze-Einstellung laden (z. B. wenn Sie beim Parametrieren ’den roten Faden’ verloren haben). EDK82EV222 DE/EN/FR 6.0...
  • Page 28 Show/Hide Bookmarks Inbetriebnahme Parametrieren mit dem Keypad Wechsel zwischenden Menüs U U U U S S S S E E E E r r r r und A A A A L L L L L L L L USEr Œ...
  • Page 29 Show/Hide Bookmarks Inbetriebnahme Parametrieren mit dem Keypad Parameter in den Menüs ändern Schritt Tasten- Display Bemerkung Beispiel folge Regler Nur notwendig, wenn Sie Codes ändern wol- sperren len, die in der Codetabelle mit “[ ]” gekenn- zeichnet sind, z. B. [C0002]. Alle anderen Parameter können Sie während des Betriebs ändern.
  • Page 30 Show/Hide Bookmarks Inbetriebnahme Parametrieren mit dem Keypad Parametersatz wechseln Wenn Sie Codes in einem Parametersatz ändern wollen, wechseln Sie über das Keypad in den entspre- chenden Parametersatz. Beachten Sie, daß einige Codes in allen Parametersätzen gleich eingestellt sind, d. h. die Einstellung in Parametersatz 1 gilt für alle Parametersätze. Diese Codes sind in der Code- tabelle mit einem “*”...
  • Page 31: Wahl Der Richtigen Betriebsart

    Show/Hide Bookmarks Inbetriebnahme Wahl der richtigen Betriebsart Für Standardanwendungen hilft Ihnen die folgende Tabelle, die richtige Betriebsart zu wählen. Sie kön- nen wählen zwischen U/f-Kennliniensteuerung, Vector-Regelung und sensorloserDrehmoment-Rege- lung: Die U/f-Kennliniensteuerung ist die klassische Betriebsart für Standardanwendungen. Mit der Vector-Regelung erzielen Sie gegenüber der U/f-Kennliniensteuerung verbesserte Antriebsei- genschaften durch: höheres Drehmoment über den gesamten Drehzahlbereich höhere Drehzahlgenauigkeit und höhere Rundlaufgüte...
  • Page 32 Show/Hide Bookmarks Inbetriebnahme Wahl der richtigen Betriebsart Anwendung Betriebsart C0014 empfohlen alternativ Einzelantriebe mit stark wechselnden Lasten mit Schweranlauf mit Drehzahlregelung (Drehzahlrückführung) mit hoher Dynamik (z. B. Positionier- und Zustellantriebe) mit Drehmoment-Sollwert mit Drehmomentbegrenzung (Leistungsregelung) Drehstrom-Reluktanzmotoren Drehstrom-Verschiebeankermotoren Drehstrommotoren mit fest zugeordneter Frequenz-Spannungskennlinie Pumpen- und Lüfterantriebe mit quadratischer Lastkennlinie -2- / -4- Gruppenantriebe...
  • Page 33: Vor Dem Ersten Einschalten

    Show/Hide Bookmarks Inbetriebnahme Vor dem ersten Einschalten Tip! Halten Sie die jeweilige Einschaltreihenfolge ein. Bei Störungen während der Inbetriebnahme hilft Ihnen das Kapitel ”Störungen erkennen und beseitigen”. Um Personenschäden oder Sachschäden zu vermeiden, überprüfen Sie ..vor dem Zuschalten der Netzspannung: Die Verdrahtung auf Vollständigkeit, Kurzschluß...
  • Page 34: Lineare U/F-Kennliniensteuerung

    Passen Sie die Klemmenkonfigura- Œ j g f k i h PS tion an die Verdrahtung an (C0007) ‚ m n o Lenze-Einstellung: -0-, d. h. E1: JOG1/3 Auswahl Festfrequenzen E2: JOG2/3 E3: DCB Gleichstrombremse E4: CW/CCW Rechtslauf/Linkslauf EDK82EV222 DE/EN/FR 6.0...
  • Page 35 13. Stellen Sie die U -Anhebung ein Die Lenze-Einstellung ist (C0016) für alle gängigen Anwen- dungen geeignet Lenze-Einstellung: hängt ab vom Antriebsreglertyp C0015 14. Wenn Sie weitere Einstellungen vor- Z. B. Festfrequenzen (JOG) (C0037, Die wichtigsten Codes im nehmen wollen, müssen Sie in das C0038, C0039), Ablaufzeit für Quick-...
  • Page 36: Vector-Regelung

    Passen Sie die Klemmenkonfigura- Œ j g f k i h PS tion an die Verdrahtung an (C0007) ‚ m n o Lenze-Einstellung: -0-, d. h. E1: JOG1/3 Auswahl Festfrequenzen E2: JOG2/3 E3: DCB Gleichstrombremse E4: CW/CCW Rechtslauf/Linkslauf EDK82EV222 DE/EN/FR 6.0...
  • Page 37 Show/Hide Bookmarks Inbetriebnahme Vector-Regelung Einschaltreihenfolge Bemerkung Stellen Sie die minimale Ausgangs- frequenz ein (C0010) C0011 Lenze-Einstellung: 0.00 Hz Stellen Sie die maximale Ausgangs- frequenz ein (C0011) C0010 Lenze-Einstellung: 50.00 Hz 100 % Stellen Sie die Hochlaufzeit T C0011 ⋅ (C0012) f 2 −...
  • Page 38 Show/Hide Bookmarks Inbetriebnahme Vector-Regelung Einschaltreihenfolge Bemerkung Geben Sie die Motordaten ein Siehe Motor-Typenschild A. Motor-Bemessungsdrehzahl (C0087) Lenze-Einstellung: 1390 rpm B. Motor-Bemessungsstrom (C0088) Wert für die gewählte Mo- tor-Schaltungsart (Stern/ Lenze-Einstellung: geräteabhängig Dreieck) eintragen! C. Motor-Bemessungsfrequenz (C0089) Lenze-Einstellung: 50 Hz D. Motor-Bemessungsspannung Wert für die gewählte Mo-...
  • Page 39 Show/Hide Bookmarks Inbetriebnahme Vector-Regelung Einschaltreihenfolge Bemerkung Stellen Sie ggf. weitere Parameter Z. B. Festfrequenzen (JOG) (C0037, C0038, C0039), Ablaufzeit für Quick- stop (QSP) (C0105) oder Motortem- peratur-Überwachung aktivieren (C0119) Wenn Sie alle Parameter eingestellt haben: Sollwert vorgeben Z. B. über Potentiometer an Klem- men 7, 8, 9 Regler freigeben Klemme X3/28 = HIGH...
  • Page 40: Vector-Regelung Optimieren

    Show/Hide Bookmarks Inbetriebnahme Vector-Regelung optimieren Die Vector-Regelung ist nach der Motorparameter-Identifizierung in der Regel ohne weitere Maßnah- men betriebsfähig. Sie müssen die Vector-Regelung nur bei folgendem Antriebsverhalten optimieren: Antriebsverhalten Abhilfe Bemerkung Rauher Motorlauf und Motorstrom 1. Motorinduktivität (C0092) um 10 % verrin- C0092 max.
  • Page 41: Codetabelle (Auszug)

    U U U U S S S S E E E E r r r r ist nach jedem Netzeinschalten aktiv. Bezeichnung Bezeichnung des Code Lenze Lenze-Einstellung (Wert bei Auslieferung oder nach Wiederherstellen des Lieferzustands mit C0002) à Die Spalte ”WICHTIG” enthält weitere Information Auswahl 99 min.
  • Page 42 Show/Hide Bookmarks Inbetriebnahme Codetabelle (Auszug) Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl Parametersatz- Bereit PAR1 ... PAR4: C0002* verwaltung Parametersätze des Antriebsreglers U U U U S S S S E E E E r r r r PAR1 ... PAR4 enthal- ten auch die Parame- ter für die Funktions-...
  • Page 43 Show/Hide Bookmarks Inbetriebnahme Codetabelle (Auszug) Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0002* Parametersätze Mit dem Keypad können mit Keypad über- Sie die Parametersätze tragen PAR1 ... PAR4 zu ande- U U U U S S S S E E E E r r r r ren Antriebsreglern über-...
  • Page 44 Show/Hide Bookmarks Inbetriebnahme Codetabelle (Auszug) Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0002* eigene Grundein- PAR1 eigene Grundeinstellung Keypad unterstützt die ð stellung spei- Funktion ab Version chern E82ZC ... BBVB12 U U U U S S S S E E E E r r r r Sie können für die Para-...
  • Page 45 Show/Hide Bookmarks Inbetriebnahme Codetabelle (Auszug) Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl Parameter nicht im EEPROM spei- Datenverlust nach C0003* Parameter nicht- chern Netzausschalten flüchtig speichern flüchtig speichern Parameter immer im EEPROM spei- Nach jedem Netzein- chern schalten aktiv Zyklisches Ändern von Parametern über...
  • Page 46 Show/Hide Bookmarks Inbetriebnahme Codetabelle (Auszug) Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0007 C0007 Feste Konfigura- Feste Konfigura CW/CCW = Rechts- CW/CCW = Rechts tion digitale Ein- lauf/Linkslauf JOG2/3 JOG1/3 gänge U U U U S S S S E E E E r r r r...
  • Page 47 Show/Hide Bookmarks Inbetriebnahme Codetabelle (Auszug) Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0007 C0007 JOG1/3, JOG2/3 = JOG1/3, JOG2/3 = Auswahl Festsoll- -11- DOWN werte werte U U U U S S S S E E E E r r r r...
  • Page 48 AIN2 gangsfrequenz U U U U S S S S E E E E r r r r 87 Hz Drehzahlstellbereich à à 1 : 6 für Lenze-Ge- triebemotoren: Bei Betrieb mit Lenze- Getriebemotoren unbe- dingt einstellen. C0012 Hochlaufzeit 5.00 0.00...
  • Page 49 Show/Hide Bookmarks Inbetriebnahme Codetabelle (Auszug) Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0017 Ansprechschwelle 0.00 0.00 {Hz} 650.00 Application-I/O unter- stützt 650 Hz ab Version E82AF ... XXVB21 Schwelle bezogen auf den Sollwert, nicht auf die aktuelle Ausgangs- frequenz! C0018 C0018...
  • Page 50 Show/Hide Bookmarks Inbetriebnahme Codetabelle (Auszug) Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0034* Bereich Sollwert- Jumperstellung des vorgabe Funktionsmoduls beachten! Application-I/O U U U U S S S S E E E E r r r r 1 X3/1U, X3/1I Spannung unipolar 0 ...
  • Page 51 Show/Hide Bookmarks Inbetriebnahme Codetabelle (Auszug) Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0061* Temperatur Kühl- { ° C} 255 Nur Anzeige körper Wenn > +80 °C: – Antriebsregler setzt O O O O H H H H Warnung – Schaltfrequenz wird...
  • Page 52 Show/Hide Bookmarks Inbetriebnahme Codetabelle (Auszug) Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0107 Haltezeit DCB 999.00 1.00 999.00 Haltezeit, wenn DCB von extern über Klemme oder = ∞ Steuerwort ausgelöst wird C0111 Konfiguration Ausgangsfrequenz mit Schlupf Weitere Einstellungen Analogausgang (MCTRL1-NOUT+SLIP) siehe Betriebsanleitung...
  • Page 53 Show/Hide Bookmarks Inbetriebnahme Codetabelle (Auszug) Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0140* Additiver Fre- -650.00 {Hz} 650.00 Application-I/O unter- quenz-Sollwert stützt 650 Hz ab Version (NSET1-NADD) E82AF ... XXVB21 Vorgabe über Funk- tion des Keypad oder Parameterkanal Wert wird nichtflüch- tig (d.
  • Page 54 Show/Hide Bookmarks Inbetriebnahme Codetabelle (Auszug) Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl Bereit Nur bei kaltem Motor C0148* Motorparameter identifizieren durchführen! 1. Regler sperren, war- ten bis Antrieb steht 2. In C0087, C0088, C0089 C0090 C0089, C0090, Identifizierung starten C0091 die korrekten...
  • Page 55 Show/Hide Bookmarks Inbetriebnahme Codetabelle (Auszug) Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl TRIP-Reset durch Netzschalten, C0170 Konfiguration TRIP-Reset über TRIP-Reset , LOW–Flanke an X3/28, über Funktionsmodul oder Funktionsmodul oder über Kommu- Kommunikationsmo- nikationsmodul dul mit C0043, dul mit C0043, C0410/12 d C0410/12 oder wie -0- und zusätzlich Auto-TRIP-...
  • Page 56 Show/Hide Bookmarks Inbetriebnahme Codetabelle (Auszug) Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0239 untere Frequenz- -650.0 -650.00 {Hz} 650.00 Application-I/O unter- begrenzung stützt 650 Hz ab Version E82AF ... XXVB21 Wird unabhängig vom Sollwert grundsätzlich nicht unterschritten C0265* Konfiguration Mo- Startwert = power off...
  • Page 57 Show/Hide Bookmarks Inbetriebnahme Codetabelle (Auszug) Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0410 Freie Konfigura- Verknüpfung externer Signalquellen tion digitale Ein- mit internen Digitalsignalen gangssignale C0412 Freie Konfigura- Verknüpfung externer analoger Si- tion analoge Ein- gnalquellen mit internen Analogsi- gangssignale gnalen...
  • Page 58 Show/Hide Bookmarks Inbetriebnahme Codetabelle (Auszug) Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0517* Nach Netzschalten Menü U U U U S S S S E E E E r r r r oder in der Funktion d i d F kti...
  • Page 59: Störungen Erkennen Und Beseitigen

    Show/Hide Bookmarks Störungen erkennen und beseitigen Fehlverhalten des Antriebs Fehlverhalten Ursache Abhilfe Motor dreht nicht Zwischenkreisspannung zu niedrig Netzspannung prüfen (Rote LED blinkt im 0.4 s Takt; Anzeige Keypad: L L L L U U U U Antriebsregler gesperrt Reglersperre aufheben, Reglersperre kann über mehrere Quellen gesetzt (Grüne LED blinkt, Anzeige Keypad: sein...
  • Page 60 Show/Hide Bookmarks Störungen erkennen und beseitigen Fehlverhalten des Antriebs Fehlverhalten Ursache Abhilfe Motor nimmt zu- Motor nimmt zu Einstellung von C0016 zu groß gewählt Einstellung korrigieren viel Strom auf viel Strom auf Einstellung von C0015 zu klein gewählt Einstellung korrigieren C0084, C0087, C0088, C0089, C0090, C0091 Manuell anpassen oder Motorparame- und/oder C0092 nicht an die Motordaten ange-...
  • Page 61: Störungsmeldungen

    Show/Hide Bookmarks Störungen erkennen und beseitigen Störungsmeldungen LED’s am Antriebsregler (Betriebszustandsanzeigen) Betriebszustand grün Antriebsregler freigegeben Netz eingeschaltet und automatischer Start gesperrt blinkt Antriebsregler gesperrt blinkt im 1-Sekunden-Takt Störung aktiv, Kontrolle in C0161 blinkt im 0,4-Sekunden-Takt Unterspannungsabschaltung blinkt schnell Motorparameter-Identifizierung wird durchgeführt Störungsmeldungen am Keypad oder im Parametrierprogramm Global Drive Control Anzeige Störung...
  • Page 62 Slave antwortet nicht. Kommu- Systembus-Konfiguration prüfen nikations-Überwachungszeit überschritten Bei Betrieb mit Modul auf FIF: Rücksprache mit Lenze erforderlich Interner Fehler Funktionsmodul CAN Controller meldet Zustand Prüfen, ob Busabschluß vorhan- c c c c e e e e 6 6 6 6 Systembus (CAN) ”Warnung”...
  • Page 63 Show/Hide Bookmarks Störungen erkennen und beseitigen Störungsmeldungen Anzeige Störung Ursache Abhilfe Keypad PC 140 Fehlerhafte Para- Motor nicht angeschlossen Motor anschließen i i i i d d d d 1 1 1 1 meter-Identifizie- rung Ausfall einer/mehrerer Mo- Motorzuleitungen prüfen Fehler in Motor- L L L L P P P P 1 1 1 1 phase...
  • Page 64 Show/Hide Bookmarks Störungen erkennen und beseitigen Störungsmeldungen Anzeige Störung Ursache Abhilfe Keypad PC Überlast Antriebs- Zu kurz eingestellte Ablaufzeit Ablaufzeit verlängern O O O O C C C C 4 4 4 4 regler im Ablauf (C0013) Auslegung des externen Brems- widerstands prüfen Überlast Antriebs- Häufige und zu lange Überlast...
  • Page 65 Show/Hide Bookmarks Störungen erkennen und beseitigen Störungsmeldungen Anzeige Störung Ursache Abhilfe Keypad PC PTC-Überwachung O O O O H H H H 3 3 3 3 Motor zu warm durch unzulässig Antriebsauslegung prüfen (TRIP) hohe Ströme oder häufige und (wird nur generiert, zu lange Beschleunigungsvor- gänge wenn...
  • Page 66 P P P P r r r r 4 4 4 4 pad falsch übertra- Interne Störung Rücksprache mit Lenze erforderlich P P P P r r r r 5 5 5 5 Zeitfehler bei Para- Datenfluß vom Keypad oder vom...
  • Page 67 Show/Hide Bookmarks Störungen erkennen und beseitigen Störungsmeldungen EDK82EV222 DE/EN/FR 6.0...
  • Page 68 – If the FIF cover is not mounted, the 8200 vector is inhibited (keypad: Since the 8200 vector does not provide any control terminals when the function module is not attached, starting and stopping during operation is also possible by switching the mains.
  • Page 69 Show/Hide Bookmarks Contents Safety instructions ......... Items supplied .
  • Page 70: Safety Instructions

    (according to Low-Voltage Directive 73/23/EEC) 1. General Lenze controllers (frequency inverters, servo inverter, DC controllers) can carry a voltage or parts of the controllers can rotate during operation. Surfaces can be hot. If the required cover is removed, the controllers are used inappropriately or installed or operated incorrectly, severe damage to persons or material assets can occur.
  • Page 71 7. Safe standstill The variant V004 of 9300 and 9300 vector, and the variant Bx4x of 8200 vector controllers support the function ”Safe standstill”, protection against unexpected start, according to the requirements of Annex I No. 1.2.7 of the EC Directive ”Machinery”...
  • Page 72: Residual Hazards

    Show/Hide Bookmarks Safety instructions Residual hazards Protection Before working on the controller check that no voltage is applied to the power terminals, the of persons relay output and the pins of the FIF interface. – because the power terminals U, V, W, BR1, BR2 and the pins of the FIF interface remain live for at least 3 minutes after mains switch-off.
  • Page 73: Layout Of The Safety Instructions

    Show/Hide Bookmarks Safety instructions Layout of the safety instructions All safety instructions given in these Operating Instructions have the same layout: (characterized the severity of danger) Signal word Note (describes the danger and gives information how to avoid it) Icons used Signal words Warning of Danger!
  • Page 74: Items Supplied

    X1.2 X2.1 X2.2 Æ 5 mm Æ 8 mm Æ 10 mm 8200vec002 8200 vector frequency inverters Mounting Instructions ¶ 15 or ¶ 17 Terminal strip X1.1: mains connection, DC-supply ¶ 19 Terminal strip X1.2: relay output Terminal strip X2.1: motor connection, brake resistor connection (optionally) ¶...
  • Page 75: Technical Data

    Show/Hide Bookmarks Technical data Conformity Low-Voltage Directive (73/23/EEC) Approvals UL 508C Underwriter Laboratories (File-No. E132659) Power Conversion Equipment as of version E82EVxxxKxBxxxXX 1F 14 Max. perm. motor cable length Max. perm. motor cable length With rated mains voltage and With rated mains voltage and shielded: 50 m chopper frequency of 8 kHz...
  • Page 76 Show/Hide Bookmarks Technical data Type Type Power Power Mains voltage Mains voltage Mains Mains Output current Weight Weight current (60 s) E82EV251K2B 0.25 kW 3.4 A 1.7 A 2.6 A 0 8 kg 0.8 kg E82EV371K2B 0.37 kW 1/N/PE AC 230/240 V 5.0 A 2.4 A 3.6 A...
  • Page 77: Mechanical Installation

    Show/Hide Bookmarks Mechanical installation Dimensions for standard fixing 4 Nm 35 lbin Abb. 1-7 8200vec004 Dimensions in Dimensions in E82EV251K2B 180 210 130...140 120...170 110...200 120 E82EV371K2B 6 5 27 5 6.5 27.5 E82EV551KxB 240 270 190...200 180...230 170...260 180 E82EV751KxB E82EV152KxB 250...260...
  • Page 78: Electrical Installation

    Show/Hide Bookmarks Electrical installation Installation according to EMC requirements Abb. 1-8 8200vec008 Stop! Control cables and mains cables must be separated from the motor cable to avoid interferences. Function module (option) Star or delta connection as indicated on the motor nameplate EMC-cable connector (not included in the delivery package) Shielded motor cable, low-capacity (core/core ≤...
  • Page 79 Show/Hide Bookmarks Electrical installation Installation according to EMC requirements Note! If the cores for motor connection and PTC or thermal contact are together in one cable with a common shield, an additional ferrite centre , type EZZ0013 is required: – Both cores of the supply cable for the PTC or thermal contact must be routed three times through the ferrite centre in direct vicinity to the terminal X2.2.
  • Page 80: Wiring Of Terminal Strips - Easy And Safe

    Show/Hide Bookmarks Electrical installation Wiring of terminal strips - easy and safe The supplied terminal strips are tested according to the specifications of the DIN VDE 0627:1986-06 (partially) DIN EN 60999:1994-04 (partially) Tested features: mechanical, electrical and thermal load, vibration, damage of conductors, loose con- ductors, corrosion, ageing.
  • Page 81: Mains Connection 230 V/240 V

    Show/Hide Bookmarks Electrical installation Mains connection 230 V/240 V Stop! Controller type E82EVxxxK 2B must only be connected to a mains voltage of 1/N/PE AC 180 ... 264 V or 3/PE AC 100 ... 264 V. Higher mains voltages will destroy the controller! The discharge current to PE is >...
  • Page 82: Mains Connection 230 V/240 V

    Show/Hide Bookmarks Electrical installation Mains connection 230 V/240 V Fuses and cable cross-sections Type Type Mains Mains Installation to EN 60204-1 Installation to UL Fuse E.l.c.b. L1, L2, L3, N, PE Fuse L1, L2, L3, N, PE [AWG] M10 A C10 A 10 A E82EV251K2B...
  • Page 83 Show/Hide Bookmarks Electrical installation Mains connection 400 V E82EV551K4B E82EV751K4B E82EV152K4B X1.1 E82EV222K4B X1.1 L3 PE +UG -UG L2/N Abb. 1-10 L1 L2 3/PE AC 400 V 8200vec011 X1.1/+UG, X1.1/-UG DC supply (DC-bus operation - see Operating Instructions) Fuses and cable cross-sections Type Type mains...
  • Page 84: Connection Of Motor / Brake Resistor

    The shorter the motor cables, the better the drive response! HF-screen end by PE connection through screen clamp or EMC cable connection. X2.1/PE Earthing of the 8200 vector at the output side X2.1/BR1, Connection terminals for the brake resistor X2.1/BR2 (For information about the operation with brake resistor see the Operating Instructions) X2.2/T1,...
  • Page 85: Connection Of Relay Output

    Electrical installation Connection of relay output Abb. 1-12 8200vec013 Function Message Relay setting Technical data switched (Lenze setting) X1.2/K11 Relay output open TRIP normally-closed contact AC 250 V/3 A AC 250 V/3 A X1.2/K12 Mid position contact DC 24 V/2 A DC 24 V/2 A ...
  • Page 86: Function Module (Optional)

    Show/Hide Bookmarks Function module (optional) Mounting Danger! The pins of the FIF interface carry dangerous voltage! Install the function module only when the controller is disconnected from the mains. After disconnection from the mains wait for at least 3 minutes before you start working on the module.
  • Page 87: Disassembly

    Show/Hide Bookmarks Function module (Option) Disassembly Dismount the function module only if it is absolutely necessary (e.g. when the controller is replaced). The pin strip which is used to connect the function module is part of the contact system of the controller. It has not been designed for repeated connection and disconnection of the function module.
  • Page 88 Show/Hide Bookmarks Function module (Option) Disassembly 1. Disconnect the controller from the mains and wait for at least 3 minutes! 2. Insert the screw driver max. 5 mm into the hole on top of the function module. max. 5 mm! 3.
  • Page 89: Communication Module (Option)

    This is also possible during operation. 8200vec073 External voltage supply As of version E82EVxxxKxBxxXX 1F 14 Internal voltage supply the communication modules can also be (Lenze setting) supplied internally supplied internally. For internal voltage supply, jumper must be connected to the position indicated.
  • Page 90: Commissioning

    C0517 menu User). The User menu – is active after every power- or keypad attachment during operation. – contains all codes for a standard application with linear V/f-characteristic control (Lenze setting). – can be modified as required under C0517. The all menu –...
  • Page 91 ( ¶ 39) Tip! Use C0002 ”Parameter set transfer” to easily transfer configurations from one controller to the other or to reset the controller to Lenze settings (if you lost track during parameter setting). EDK82EV222 DE/EN/FR 6.0...
  • Page 92 Show/Hide Bookmarks Commissioning Parameter setting using the keypad Change between U U U U S S S S E E E E r r r r and A A A A L L L L L L L L USEr Œ...
  • Page 93 Show/Hide Bookmarks Commissioning Parameter setting using the keypad Parameter change in menus Step Keys Display Note Example Controller Only necessary if you want to change codes inhibit marked with “[ ]” in the code table, e. g. [C0002]. All other parameters can be changed during operation.
  • Page 94 Show/Hide Bookmarks Commissioning Parameter setting using the keypad Parameter set change If you want to change the codes of a parameter set, change to the parameter set using the keypad. Please observe that some codes are set in the same way in all parameter sets, i.e. the setting of parameter set 1 applies to all parameter sets.
  • Page 95: Selection Of The Correct Control Mode

    Show/Hide Bookmarks Commissioning Selection of the correct control mode The following table helps you to find the correct control mode for standard applications. You can choose between V/f-characteristic control, vector control and sensorless torque control: V/f-characteristic control is the classic control mode for standard applications. The vector control provides better control features than the V/f-characteristic control because of: a higher torque over the whole speed range higher speed accuracy and smooth running features...
  • Page 96 Show/Hide Bookmarks Commissioning Selection of the correct control mode Application Operating mode C0014 recommended alternatively Stand-alone drives with extremely alternating loads with heavy start conditions with speed control (speed feedback) with high dynamic response (e. g. positioning and infeed drives) with torque setpoint with torque limitation (power control) three-phase AC reluctance motors...
  • Page 97: Before Switching On

    Show/Hide Bookmarks Commissioning Before switching on Note! Do not change the switch-on sequence. In the event of an error during commissioning please see the chapter ”Fault detection and elimination”. Check the following to avoid damage to persons or material..before the mains voltage is connected: Completeness, short circuit and earth fault ”Emergency-off”...
  • Page 98: Linear V/F-Characteristic Control

    PS range to the analog setpoint (C0034) standard-I/O to the same ‚ m n o range (see Mounting Lenze setting: -0-, (0 ... 5 V/0 ... 10 Instructions for the V/0 ... 20 mA) standard-I/O) Adapt the terminal configuration to Œ...
  • Page 99 Lenze setting: 50.00 Hz 100% 13. Set the V boost (C0016) The Lenze setting is suitable for all common Lenze settings: Depending on the applications controller type C0015 14. If you want to change the settings, E.g. JOG frequencies (C0037,...
  • Page 100: Vector Control

    Adapt the terminal configuration to Œ j g f k i h PS the wiring (C0007) ‚ m n o Lenze setting: -0-, i. e. E1: JOG1/3 JOG frequency selection E2: JOG2/3 E3: DCB DC brake E4: CW/CCW operation EDK82EV222 DE/EN/FR 6.0...
  • Page 101 PS the analog setpoint (C0034) standard-I/O to the same ‚ m n o range (see Mounting Lenze setting: -0-, (0 ... 5 V/0 ... 10 Instructions for the V/0 ... 20 mA) standard-I/O) EDK82EV222 DE/EN/FR 6.0...
  • Page 102 A. Rated motor speed (C0087) Lenze setting: 1390 rpm B. Rated motor current (C0088) Enter the value for the motor connection type Lenze setting: Depending on the (star/delta) selected! controller C. Rated motor frequency (C0089) Lenze setting: 50 Hz D. Rated motor voltage (C0090)
  • Page 103 Show/Hide Bookmarks Commissioning Vector control Switch-on sequence Note If necessary, adjust more E. g. JOG frequencies (C0037, parameters C0038, C0039), deceleration time for quick stop (QSP) (C0105) or motor temperature monitoring (C0119) After parameter setting: Setpoint selection E.g. via potentiometer at terminals 7, 8, 9 Enable the controller.
  • Page 104: Vector Control Optimisation

    Show/Hide Bookmarks Commissioning Vector control optimisation The vector control is usually ready for operation after the motor parameter identification. Vector control must only be optimised for the following drive performance: Drive response Remedy Note Rough motor run and motor current 1.
  • Page 105: Code Table (Excerpt)

    U U U U S S S S E E E E r r r r With Lenze setting the code is available in the menu U U U U S S S S E E E E r r r r .
  • Page 106 Module-specific parameter set of PROFIBUS-DP, INTERBUS, DeviceNet/CANopen or LECOM-B FPAR1 is saved in the function module Restorage of Restorage of Lenze setting PAR1 Restorage of default Restorage of default ð default setting setting in the selected Lenze setting PAR2 ð...
  • Page 107 Show/Hide Bookmarks Commissioning Code table (excerpt) Code Possible settings IMPORTANT Name Lenze Choice C0002* Parameter set Use the keypad to transfer using the transfer parameter sets keypad PAR1 ... PAR4 to other U U U U S S S S E E E E r r r r...
  • Page 108 Show/Hide Bookmarks Commissioning Code table (excerpt) Code Possible settings IMPORTANT Name Lenze Choice C0002* Saving of own PAR1 Own settings Keypad supports this ð settings function as of version E82ZC ... BBVB12 U U U U S S S S E E E E r r r r You can save your own (cont.)
  • Page 109 Show/Hide Bookmarks Commissioning Code table (excerpt) Code Possible settings IMPORTANT Name Lenze Choice Parameter not saved in EEPROM Data loss after mains C0003* Non-volatile disconnection parameter saving parameter saving Parameter always saved in EEPROM Active after every main connection Cyclic parameter...
  • Page 110 Show/Hide Bookmarks Commissioning Code table (excerpt) Code Possible settings IMPORTANT Name Lenze Choice C0007 C0007 Fixed Fixed CW/CCW = CW CW/CCW = CW configuration of rotation/CCW rotation JOG2/3 JOG1/3 digital inputs U U U U S S S S E E E E r r r r...
  • Page 111 Show/Hide Bookmarks Commissioning Code table (excerpt) Code Possible settings IMPORTANT Name Lenze Choice C0007 C0007 JOG1/3, JOG2/3 = JOG1/3, JOG2/3 = Selection of fixed -11- DOWN setpoints setpoints U U U U S S S S E E E E r r r r...
  • Page 112 87 Hz Speed setting range U U U U S S S S E E E E r r r r à à 1 : 6 for Lenze geared motors: Setting absolutely required for operation with Lenze geared motors.
  • Page 113 Show/Hide Bookmarks Commissioning Code table (excerpt) Code Possible settings IMPORTANT Name Lenze Choice C0016 boost 0.00 40.0 depending on the à à controller U U U U S S S S E E E E r r r r Setting applies to all...
  • Page 114 Show/Hide Bookmarks Commissioning Code table (excerpt) Code Possible settings IMPORTANT Name Lenze Choice C0034* Setpoint selection Observe the jumper range setting of the function module! Application I/O U U U U S S S S E E E E r r r r 1 X3/1U, X3/1I Voltage unipolar 0 ...
  • Page 115 Show/Hide Bookmarks Commissioning Code table (excerpt) Code Possible settings IMPORTANT Name Lenze Choice C0052* Motor voltage 1000 (MCTRL1-VOLT) C0053* DC bus voltage 1000 (MCTRL1-DCVOLT) Only display Only display C0054* Apparent motor current (MCTRL1-IMOT) C0056* Unit load -255 C0061* Heat sink { °...
  • Page 116 Show/Hide Bookmarks Commissioning Code table (excerpt) Code Possible settings IMPORTANT Name Lenze Choice C0105 Deceleration time 5.00 0.00 1300.00 Quick stop decelerates quick stop (QSP) the drive to standstill according to the deceleration time set under C0105. If the output frequency falls...
  • Page 117 Show/Hide Bookmarks Commissioning Code table (excerpt) Code Possible settings IMPORTANT Name Lenze Choice C0120 t switch-off 200 Reference: Apparent motor current (C0054) = not active C0140* Added frequency -650.00 {Hz} 650.00 Application I/O supports setpoint 650 Hz as of version (NSET1-NADD) E82AF ...
  • Page 118 Show/Hide Bookmarks Commissioning Code table (excerpt) Code Possible settings IMPORTANT Name Lenze Choice Ready Only when the motor is C0148* Motor parameter identification cold! 1. Inhibit controller, wait until drive is in standstill 2. Enter the correct 2. Enter the correct...
  • Page 119 Show/Hide Bookmarks Commissioning Code table (excerpt) Code Possible settings IMPORTANT Name Lenze Choice TRIP reset by mains switching, C0170 Configuration TRIP reset via TRIP reset , LOW–signal at X3/28, via function module or function module or communication communication module module with C0043,...
  • Page 120 Show/Hide Bookmarks Commissioning Code table (excerpt) Code Possible settings IMPORTANT Name Lenze Choice C0239 Lowest frequency -650.0 -650.00 {Hz} 650.00 Application I/O supports limit 650 Hz as of version E82AF ... XXVB21 The value does not fall below limit independently of the setpoint.
  • Page 121 Show/Hide Bookmarks Commissioning Code table (excerpt) Code Possible settings IMPORTANT Name Lenze Choice C0410 Free configuration Linkage of external signal sources of digital input to internal digital signals signals C0412 Free configuration Connection between external analog of analog input signal sources and internal analog...
  • Page 122 Show/Hide Bookmarks Commissioning Code table (excerpt) Code Possible settings IMPORTANT Name Lenze Choice C0517* After mains switching Menu U U U U S S S S E E E E r r r r or when using the or when using the...
  • Page 123: Fault Detection And Elimination

    Show/Hide Bookmarks Fault detection and elimination Faulty drive behaviour Fault Cause Remedy Motor does not DC-bus voltage too low Check mains voltage rotate (Red LED is blinking every 0.4 s; keypad display L L L L U U U U Controller inhibited Remove the controller inhibit, controller inhibit can be set through...
  • Page 124 Show/Hide Bookmarks Fault detection and elimination Faulty drive behaviour Fault Cause Remedy Current Current Setting of C0016 too high Correct setting consumption of consumption of Setting of C0015 too low Correct setting motor too high C0084, C0087, C0088, C0089, C0090, C0091 Manual adaptation or identification of and/or C0092 are not adapted to the motor data motor parameters (C0148)
  • Page 125: Fault Messages

    Show/Hide Bookmarks Fault detection and elimination Fault messages LEDs at the controller (operating status display) Operating status green Controller enabled Mains switched on and automatic start inhibited blinking Controller inhibited blinking every second Fault active, check under C0161 blinking every 0.4 seconds Undervoltage switch-off fast blinking Motor parameter identification...
  • Page 126 (C0370): Check system bus configuration Slave does not answer. Communication monitoring time exceeded. For operation with module in Contact Lenze FIF: Internal fault Function module CAN controller sets ”Warning” or Check whether bus terminator c c c c e e e e 6 6 6 6 system bus (CAN) ”BUS OFF”...
  • Page 127 Show/Hide Bookmarks Fault detection and elimination Fault messages Display Fault Cause Remedy Keypad PC 140 Faulty parameter Motor not connected Connect motor i i i i d d d d 1 1 1 1 identification Failure of one/several motor Check motor cables, Fault in motor L L L L P P P P 1 1 1 1 phase...
  • Page 128 Show/Hide Bookmarks Fault detection and elimination Fault messages Display Fault Cause Remedy Keypad PC Controller overload Frequent and long overload Check drive selection O O O O C C C C 5 5 5 5 in stationary operation Motor overload Motor is thermally overloaded, O O O O C C C C 6 6 6 6 x t overload)
  • Page 129 It is absolutely necessary to repeat Faulty parameter All parameter sets are defective P P P P r r r r the data transfer or load the Lenze transfer when using setting before enabling the controller. the keypad Wrong PAR1 PAR1 is defective.
  • Page 130 Show/Hide Bookmarks Fault detection and elimination Fault messages Display Fault Cause Remedy Keypad PC Faulty auto-TRIP More than 8 fault messages in Depends on the fault message r r r r S S S S t t t t reset 10 minutes Open circuit in Current at analog input <...
  • Page 131 Show/Hide Bookmarks Fault detection and elimination Fault messages EDK82EV222 DE/EN/FR 6.0...
  • Page 132: Mise En Service 8200 Vector Sans Module De Fonction

    – En absence du capot de protection FIF, le 8200 vector est bloqué (clavier : Sans module de fonction le 8200 vector ne dispose pas de bornier de commande. Le démarrage et l’arrêt pendant le fonctionnement peuvent alors aussi être réalisés par coupure/rebranchement réseau.
  • Page 133 Show/Hide Bookmarks Table des matières Consignes de sécurité ........Equipement livré...
  • Page 134: Consignes De Sécurité

    Conformes à la directive Basse Tension 73/23/CEE 1. Généralités Selon leur degré de protection, les variateurs de vitesse Lenze (convertisseurs de fréquence, servovariateurs, variateurs de vitesse) peuvent avoir, pendant leur fonctionnement, des parties sous tension, éventuellement en mouvement ou tournantes. Les surfaces risquent d’être chaudes.
  • Page 135 7. Arrêt sécurisé La variante V004 des variateurs de vitesse 9300 et 9300 vector, et la variante Bx4x du variateur de vitesse 8200 vector intègre la fonction ”Arrêt sécurisé” qui englobe la protection contre un démarrage incontrôlé selon l’annexe I n° 1.2.7 de la directive CE relative aux machines 98/37/CE, DIN EN 954-1 catégorie 3 et DIN EN 1037.
  • Page 136: Dangers Résiduels

    Les entraînements peuvent atteindre des survitesses dangereuses (exemple : réglage de fréquences de sortie élevées en utilisant des moteurs et machines non adaptés). – Les convertisseurs de fréquence 8200 vector ne sont pas protégés contre de telles conditions de fonctionnement. Prévoir des composants supplémentaires.
  • Page 137: Présentation Des Consignes De Sécurité

    Show/Hide Bookmarks Consignes de sécurité Présentation des consignes de sécurité Toutes les consignes de sécurité sont présentées de façon identique : Le mot indique l’intensité du risque encouru. Avertissement L’explication décrit la gravité de ce risque et la façon d’éviter le risque. Pictogramme utilisé...
  • Page 138: Equipement Livré

    X1.2 X2.1 X2.2 Æ 5 mm Æ 8 mm Æ 10 mm 8200vec002 Convertisseur de fréquence 8200 vector Instructions de montage ¶ 15 et ¶ 17 Bornier X1.1 : Raccordement réseau, alimentation CC ¶ 19 Bornier X1.2 : Sortie relais Bornier X2.1 : Raccordement moteur, raccordement résistance de...
  • Page 139: Spécifications Techniques

    Show/Hide Bookmarks Spécifications techniques Conformité Directive Basse Tension (73/23/CEE) Homologations UL 508C Underwriter Laboratories (File-No. E132659) Power Conversion Equipment à partir de la version E82EVxxxKxBxxxXX 1F 14 Longueur de câble moteur maxi Longueur de câble moteur maxi Câble blindé : 50 m Avec une tension nominale Avec une tension nominale...
  • Page 140 Show/Hide Bookmarks Spécifications techniques Type Type Puissance Puissance Tension d’alimentation Tension d alimentation Courant Courant Courant de sortie Poids Poids réseau Limitation Limitation (60 s) E82EV251K2B 0,25 kW 3,4 A 1,7 A 2,6 A 0 8 kg 0,8 kg E82EV371K2B 0,37 kW 5,0 A 2,4 A...
  • Page 141: Installation Mécanique

    Show/Hide Bookmarks Installation mécanique Encombrements avec fixation standard 4 Nm 35 lbin Abb. 1-13 8200vec004 Cotes en mm Cotes en mm E82EV251K2B 180 210 130...140 120...170 110...200 120 E82EV371K2B 6 5 27 5 6,5 27,5 E82EV551KxB 240 270 190...200 180...230 170...260 180 E82EV751KxB E82EV152KxB 250...260...
  • Page 142: Installation Électrique

    Show/Hide Bookmarks Installation électrique Installation conforme CEM Abb. 1-14 8200vec008 Stop ! Veiller à ce que les câbles de commande et les câbles réseau ne passent pas dans les mêmes canalisations que les câbles moteur afin d’éviter des interférences radio. Module de fonction (option) Couplage étoile ou triangle comme indiqué...
  • Page 143 Show/Hide Bookmarks Installation électrique Installation conforme CEM Conseil ! Lorsque les conducteurs pour le raccordement puissance du moteur et les conducteurs pour le raccordement de la sonde PTC ou du contact thermique se trouvent dans le même câble avec blindage commun, il faut installer, en plus une ferrite type EZZ0013.
  • Page 144: Câblage Des Borniers - Simple Et Efficace

    Show/Hide Bookmarks Installation électrique Câblage des borniers - simple et efficace Les borniers compris dans la livraison ont été vérifiés conformément aux normes et réglementations suivantes : DIN VDE 0627 : 1986-06 (en partie) DIN EN 60999 : 1994-04 (en partie) Les borniers ont été...
  • Page 145: Raccordement Réseau 230 V/240 V

    Show/Hide Bookmarks Installation électrique Raccordement réseau 230 V/240 V Stop ! Ne raccorder le variateur type E82EVxxxK 2B qu’au réseau 1/N/PE CA 180 ... 264 V ou 3/PE CA 100 ... 264 V. Toute tension réseau plus élevée risque de détruire le convertisseur ! Le courant de fuite vers la terre (PE) est de >...
  • Page 146: Raccordement Réseau 230 V/240 V

    Show/Hide Bookmarks Installation électrique Raccordement réseau 230 V/240 V Fusibles et sections de câbles Type Type Réseau Réseau Installation selon EN 60204-1 Installation selon UL Fusible Disjoncteur L1, L2, L3, N, PE Fusible L1, L2, L3, N, PE fusible [AWG] M10 A C10 A 10 A...
  • Page 147 Show/Hide Bookmarks Installation électrique Raccordement réseau 400 V E82EV551K4B E82EV751K4B E82EV152K4B X1.1 E82EV222K4B X1.1 L3 PE +UG -UG L2/N Abb. 1-16 L1 L2 3/PE AC 400 V 8200vec011 X1.1/+UG, X1.1/-UG Alimentation CC (fonctionnement de plusieurs appareils en réseau CC, voir instructions de mise en service) Fusibles et sections de câbles Type...
  • Page 148: Raccordement Moteur/Résistance Externe

    En utilisant des câbles moteur aussi courts que possible les caractéristiques d’entraînement se trouvent améliorées! Raccordement HF via connexion avec PE par collier de blindage X2.1/PE Mise à la terre côté sortie du 8200 vector X2.1/BR1, Bornes de raccordement pour résistance de freinage (description du fonctionnement avec X2.1/BR2 résistance de freinage : voir instructions de mise en service)
  • Page 149: Raccordement Sortie Relais

    Raccordement sortie relais Abb. 1-18 8200vec013 Fonction Message Position relais Spécifications techniques commutée (réglage Lenze) X1.2/K11 Sortie relais (contact à Ouvert Défaut TRIP ouverture) 250 V/3 A CA 250 V/3 A CA X1.2/K12 Contact central relais 24 V/2 A CC 24 V/2 A CC ...
  • Page 150: Module De Fonction (Option)

    Show/Hide Bookmarks Module de fonction (option) Montage Danger ! Les broches de l’interface FIF sont sous tension ! Ne monter le module de fonction que l’appareil coupé du réseau ! Après la coupure du réseau, attendre 3 minutes au minimum avant toute opération. 1.
  • Page 151: Démontage

    Show/Hide Bookmarks Module de fonction (option) Démontage Déclipser le module de fonction uniquement si le démontage s’impose (exemple : échange du variateur). Le connecteur à broches dans lequel est enfiché le module de fonction sert à compléter l’appareil. Il n’est pas conçu pour enficher et retirer fréquemment le module de fonction ! Danger ! Les broches de l’interface FIF sont sous tension ! Ne démonter le module de fonction que l’appareil coupé...
  • Page 152 Show/Hide Bookmarks Module de fonction (option) Démontage 1. Couper le variateur du réseau et attendre 3 minutes au minimum ! 2. Insérer le tournevis dans l’ouverture sur le haut du module de fonction de 5 mm max. 5 mm! au maximum. 3.
  • Page 153: Module De Communication (Option)

    Show/Hide Bookmarks Module de communication (option) Montage/démontage Enficher le module de communication dans l’interface AIF ou le retirer. (Cette opération peut s’effectuer pendant le fonctionnement.) 8200vec073 Alimentation externe A partir de la version E82EVxxxKxBxxXX Alimentation via source de 1F 14, les modules de communication tension interne (état à...
  • Page 154: Mise En Service

    Show/Hide Bookmarks Mise en service Paramétrage à l’aide du clavier de commande Le clavier est disponible en option. Pour la description complète du clavier de commande, se reporter à la feuille comprise dans l’emballage du clavier. Touches de fonction Affichages d’états Affichage code de barres Barre de fonction 1 Barre de fonction 2...
  • Page 155 à la livraison en programmant le réglage Lenze (si, par exemple, pendant le paramétrage vous ne savez plus où vous en êtes et que vous souhaitez recommencer vos réglages).
  • Page 156 Show/Hide Bookmarks Mise en service Paramétrage à l’aide du clavier de commande Comment passer du menu U U U U S S S S E E E E r r r r à A A A A L L L L L L L L et vice versa USEr Œ...
  • Page 157: Comment Modifier Les Paramètres

    Show/Hide Bookmarks Mise en service Paramétrage à l’aide du clavier de commande Comment modifier les paramètres Action Séquence Affichage Remarque Exemple touches Bloquer le Uniquement nécessaire pour modifier les variateur. codes marqués par “[ ]” dans le tableau des codes (exemple : [C0002]). Tous les autres paramètres peuvent être modifiés pendant le fonctionnement.
  • Page 158 Show/Hide Bookmarks Mise en service Paramétrage à l’aide du clavier de commande Changement du jeu de paramètres Il est possible de changer de jeu de paramètres pour modifier les paramètres souhaités. Noter que certains codes sont identiques pour tous les jeux de paramètres, ce qui implique que le réglage dans le jeu de paramètres 1 est valable pour tous les jeux de paramètres.
  • Page 159: Choisir Le Mode De Fonctionnement Optimal

    Show/Hide Bookmarks Mise en service Choisir le mode de fonctionnement optimal Le tableau suivant vous permet de sélectionner le mode de fonctionnement approprié pour votre application standard. Vous pouvez choisir le fonctionnement en U/f, le contrôle vectoriel ou la régulation de couple sans capteur. Le fonctionnement en U/f est le mode de fonctionnement classique pour les applications standard.
  • Page 160 Show/Hide Bookmarks Mise en service Choisir le mode de fonctionnement optimal Applications Mode de fonctionnement C0014 Recommandation Au choix Entraînements individuels Avec charges variables fréquentes Avec démarrage dans des conditions sévères Avec régulation de vitesse (bouclage de vitesse) Avec dynamique élevée (exemple : entraînements de positionnement et d’approche) Avec consigne de couple Avec limitation de couple (régulation de puissance)
  • Page 161: Avant La Première Mise En Service

    Show/Hide Bookmarks Mise en service Avant la première mise en service Conseil ! Respecter l’ordre des opérations ! En cas de problèmes lors de la mise en service, consulter le chapitre ”Détection et élimination des défauts” : Afin d’éviter des dommages corporels et matériels, vérifier ..
  • Page 162: Fonctionnement En U/F Avec Courbe Linéaire

    DIP sur le ‚ m n o analogique (C0034). module E/S standard (voir instructions de montage Réglage Lenze : -0-, (0 ... 5 V/0 ... E/S standard). 10 V/0 ... 20 mA) Adapter la configuration des bornes Œ j g f k i h PS au câblage (C0007).
  • Page 163 Réglage Lenze : 50.00 Hz 13. Régler l’accroissement U Le réglage Lenze est (C0016). adapté à toutes les applications courantes. Réglage Lenze : en fonction du type de variateur. C0015 14. Pour procéder à d’autres Exemples : activation des Pour l’explication des fréquences fixes (JOG) (C0037,...
  • Page 164 Show/Hide Bookmarks Mise en service Fonctionnement en U/f avec courbe linéaire Ordre des opérations Remarque Après modification de tous les paramètres souhaités 15. Entrer la consigne. Exemple : via potentiomètre, sur les bornes 7, 8, 9 16. Débloquer le variateur. Borne X3/28 = HAUT 17.
  • Page 165: Contrôle Vectoriel

    Adapter la configuration des bornes Œ j g f k i h PS au câblage (C0007). ‚ m n o Réglage Lenze : -0-, c’est-à-dire E1 : JOG1/3 Sélection fréquences fixes E2 : JOG2/3 E3 : Freinage courant continu FreinCC...
  • Page 166 Mise en service Contrôle vectoriel Ordre des opérations Remarque Régler la fréquence de sortie mini (C0010). C0011 Réglage Lenze : 0.00 Hz Régler la fréquence de sortie maxi (C0011). C0010 Réglage Lenze : 50.00 Hz 100 % Régler le temps d’accélération T C0011 ⋅...
  • Page 167 A. Vitesse nominale moteur (C0087) Réglage Lenze : 1390 min-1 B. Courant nominal (C0088) Entrer la valeur pour le couplage moteur Réglage Lenze : en fonction de (étoile/triangle) choisi ! l’appareil C. Fréquence nominale moteur (C0089) Réglage Lenze : 50 Hz D.
  • Page 168 Show/Hide Bookmarks Mise en service Contrôle vectoriel Ordre des opérations Remarque Identifier les paramètres moteur Œ j g f k i h PS (C0148). ‚ m n o A. S’assurer que le blocage variateur soit activé (borne X3/28 = BAS) B.
  • Page 169: Optimiser Le Contrôle Vectoriel

    Show/Hide Bookmarks Mise en service Optimiser le contrôle vectoriel Après l’identification des paramètres moteur, le contrôle vectoriel peut appliqué, en général, sans mesure supplémentaire. L’optimisation du contrôle vectoriel s’impose uniquement pour les cas suivants : Caractéristiques d’entraînement Remède Remarque Service dur du moteur et courant 1.
  • Page 170: Tableau Des Codes (Extrait)

    U U U U S S S S E E E E r r r r est actif après chaque mise sous tension. Désignation Désignation du code Lenze Réglage Lenze (réglage usine à la livraison ou après retour au réglage usine par C0002) La colonne ”IMPORTANT” contient des informations supplémentaires. à Choix 99 Valeur mini {unité}...
  • Page 171 INTERBUS, DeviceNet/CANopen ou LECOM-B FPAR1 est sauvegardé dans le module de fonction. Retour au réglage Retour au réglage Réglage Lenze PAR1 Retour au réglage usine Retour au réglage usine ð usine (état à la du jeu de paramètres Réglage Lenze PAR2 ð...
  • Page 172 Show/Hide Bookmarks Mise en service Tableau des codes (extrait) Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0002* Transfert de jeux Le transfert des jeux de de paramètres via paramètres PAR1 ... clavier PAR4 vers d’autres U U U U S S S S E E E E r r r r variateurs est réalisé...
  • Page 173 Show/Hide Bookmarks Mise en service Tableau des codes (extrait) Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0002* Sauvegarder PAR1 Votre propre réglage de Fonction proposée par le ð votre propre base clavier à partir de la réglage de base...
  • Page 174 Show/Hide Bookmarks Mise en service Tableau des codes (extrait) Code Réglages possibles IMPORTANT N° Désignation Lenze Choix Fonction proposée par le C0002* Charger/copier clavier à partir de la votre propre réglage de base version U U U U S S S S E E E E r r r r E82ZC ...
  • Page 175 Show/Hide Bookmarks Mise en service Tableau des codes (extrait) Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0007 Configuration fixe H/AH = Sens des entrées des entrées horaire/antihoraire i / tih H/AH FreinCC JOG2/3 JOG1/3 numériques numériques U U U U S S S S E E E E r r...
  • Page 176 Show/Hide Bookmarks Mise en service Tableau des codes (extrait) Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0007 JOG1/3, JOG2/3 = Sélection fréquences Sélection fréquences -11- H/AH FreinCC +vite -vite fixes fixes U U U U S S S S E E E E r r r r...
  • Page 177 à Plage de réglage de à vitesse 1 : 6 pour motoréducteurs Lenze Réglage impératif pour fonctionnement avec motoréducteurs Lenze C0012 Temps 5.00 0.00 1300.00 Référence : Modification d’accélération de la fréquence U U U U S S S S E E E E r r r r pour consigne 0 Hz ...
  • Page 178 Show/Hide Bookmarks Mise en service Tableau des codes (extrait) Code Réglages possibles IMPORTANT N° Désignation Lenze Choix Fonctionnement en U/f U ~ f Courbe linéaire avec C0014 Mode de accroissement constant fonctionnement Fonctionnement en U/f U ~ f Courbe quadratique avec accroissement constant Contrôle vectoriel...
  • Page 179 Show/Hide Bookmarks Mise en service Tableau des codes (extrait) Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0019 Seuil de réponse 0.10 0.00 {Hz} 650.00 650 Hz possible avec E/S freinage CC application à partir de la automatique version E82AF ...
  • Page 180 Show/Hide Bookmarks Mise en service Tableau des codes (extrait) Code Réglages possibles IMPORTANT N° Désignation Lenze Choix Préréglage tension de freinage par C0035* Sélection freinage C0036 Préréglage courant de freinage par C0036 C0036 Tension/courant 150 % En fonction de à...
  • Page 181 Show/Hide Bookmarks Mise en service Tableau des codes (extrait) Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0061* Température { ° C} 255 Seulement en affichage radiateur Avec > +80 °C : – Le variateur affiche ”Avertissement” O O O O H H H H –...
  • Page 182 Show/Hide Bookmarks Mise en service Tableau des codes (extrait) Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0105 Temps d’arrêt 5.00 0.00 1300.00 La fonction ”arrêt rapide (AR) rapide” entraîne une décélération de l’entraînement jusqu’à l’arrêt selon la rampe réglée en C0105. Le freinage courant continu est activé...
  • Page 183 Show/Hide Bookmarks Mise en service Tableau des codes (extrait) Code Réglages possibles IMPORTANT N° Désignation Lenze Choix Entrée PTC C0119 Configuration de Détection de Désactiver la fonction désactivée, l’entrée PTC/de la l entrée PTC/de la mise à la terre mise à la terre détection de mise à...
  • Page 184 Show/Hide Bookmarks Mise en service Tableau des codes (extrait) Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0140* Consigne de -650.00 {Hz} 650.00 650 Hz possible avec E/S fréquence application à partir de la additive version (NSET1-NADD) E82AF ... XXVB21.
  • Page 185 Show/Hide Bookmarks Mise en service Tableau des codes (extrait) Code Réglages possibles IMPORTANT N° Désignation Lenze Choix Fréquence de sortie maxi (C0011) ... C0143* Sélection La vitesse moteur est 0 Hz redémarrage à la redémarrage à la cherchée dans la plage cherchée dans la plage...
  • Page 186 Show/Hide Bookmarks Mise en service Tableau des codes (extrait) Code Réglages possibles IMPORTANT N° Désignation Lenze Choix Prêt Ne procéder à C0148* Identification paramètres l’identification que sur moteur un moteur froid ! 1. Bloquer le variateur, attendre que l’entraînement s’arrête.
  • Page 187 Show/Hide Bookmarks Mise en service Tableau des codes (extrait) Code Réglages possibles IMPORTANT N° Désignation Lenze Choix Réarmement défaut (TRIP-Reset) C0170 Configuration Réarmement défaut par coupure et rebranchement TRIP-Reset (TRIP-Reset) par (réarmement réseau, , signal BAS sur module de fonction défaut)
  • Page 188 Show/Hide Bookmarks Mise en service Tableau des codes (extrait) Code Réglages possibles IMPORTANT N° Désignation Lenze Choix Sans défaut C0183* C0183 Diagnostic Diagnostic Seulement en affichage Seulement en affichage Défaut ”TRIP” actif O O O O U U U U Message ”surtension (...
  • Page 189 Show/Hide Bookmarks Mise en service Tableau des codes (extrait) Code Réglages possibles IMPORTANT N° Désignation Lenze Choix Valeur de départ = power off C0265* Configuration du Valeur de départ : potentiomètre Fréquence de sortie à moteur atteindre à la mise...
  • Page 190 Show/Hide Bookmarks Mise en service Tableau des codes (extrait) Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0410 Configuration Interconnexion de sources signaux libre des signaux externes avec des signaux d’entrées numériques internes numériques C0412 Configuration Interconnexion de sources signaux...
  • Page 191 Mise en service Tableau des codes (extrait) Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0517* C0517 Après la mise sous Après la mise sous Menu U U U U S S S S E E E E r r r r tension ou avec la Mémoire 1...
  • Page 192: Détection Et Élimination Des Défauts

    Show/Hide Bookmarks Détection et élimination des défauts Anomalie de fonctionnement de l’entraînement Anomalie de Origine Remède fonctionnement Le moteur ne Tension circuit intermédiaire trop faible Vérifier la tension réseau. tourne pas. (la LED rouge clignote (cycle de 0,4 s) L L L L U U U U affichage clavier : Variateur bloqué...
  • Page 193 Show/Hide Bookmarks Détection et élimination des défauts Anomalie de fonctionnement de l’entraînement Anomalie de Origine Remède fonctionnement Le courant Le courant Réglage de C0016 trop important Corriger les réglages. absorbé par le absorbé par le Réglage de C0015 trop faible Corriger les réglages.
  • Page 194: Messages Défauts

    Show/Hide Bookmarks Détection et élimination des défauts Messages défauts LEDs sur le variateur (affichage de l’état de fonctionnement) Etat de fonctionnement verte rouge ALLUMEE ETEINTE Variateur débloqué ALLUMEE ALLUMEE Mise sous tension et blocage démarrage automatique CLIGNOTE ETEINTE Variateur bloqué ETEINTE CLIGNOTE (cycle de 1 s) Défaut actif, contrôle en C0161...
  • Page 195 L’esclave ne répond pas. Temps Vérifier la configuration bus de surveillance communication système. dépassé En fonctionnement avec module Contacter votre service Lenze. sur FIF : Défaut interne Le module de Le régulateur CAN affiche l’état Vérifier la terminaison du bus.
  • Page 196 E E E E E E E E r r r r (TRIP-SET) la fonction ”mise en défaut” (TRIP-Set) a été activé. 105 Défaut interne Contacter votre service Lenze. H H H H 0 0 0 0 5 5 5 5 140 Identification de Moteur non connecté Raccorder le moteur.
  • Page 197 Show/Hide Bookmarks Détection et élimination des défauts Messages défauts Affichage Défaut Origine Remède Clavier PC Court-circuit O O O O C C C C 1 1 1 1 Court-circuit Chercher la cause du court-circuit ; vérifier le câble moteur. Vérifier la résistance de freinage. Courant de charge capacitif du Utiliser des câbles moteurs plus câble moteur trop élevé...
  • Page 198 Show/Hide Bookmarks Détection et élimination des défauts Messages défauts Affichage Défaut Origine Remède Clavier PC Surcharge moteur O O O O C C C C 6 6 6 6 Surcharge thermique du moteur. (surcharge I x t) Causes possibles : Courant permanent Vérifier le dimensionnement de inadmissible...
  • Page 199 PAR4 défectueux P P P P r r r r 4 4 4 4 de commande de PAR4 erroné Défaut interne Contacter votre service Lenze. P P P P r r r r 5 5 5 5 EDK82EV222 DE/EN/FR 6.0...
  • Page 200 été interrompu (exemple : le transfert de données ou charger le clavier de commande a été réglage Lenze. retiré pendant le transfert). Erreur réarmement Plus de 8 messages défauts en En fonction du message défaut...
  • Page 201 Show/Hide Bookmarks Détection et élimination des défauts Messages défauts EDK82EV222 DE/EN/FR 6.0...