7
Commissioning
Using the keypad XT EMZ9371BC − Vector control
Switch−on sequence
14.
Start the motor paramter identification (C0148)
A
Ensure that the controller is inhibited
B
Set C0148 = 1
C
Enable the controller.
D
If the segment becomes active after approx.
c
30 s,
inhibit the controller once again.
15.
Activate the motor temperature monitoring
(C0119), if a PTC or thermal contact is
connected to the terminal X2.2
Lenze setting: switched−off
16.
Setpoint selection
17.
Enable the controller.
18.
The drive should be running now
)
Note!
In the menu "Diagnostic" the most important drive parameters can be
monitored
138
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Note
Only when the motor is cold!
Terminal X3/28 = LOW
X3
20
28
misc001
TV
press
X3
l
Terminal X3/28 = HIGH
20
28
misc002
l
The identification starts:
– The segment
– The motor makes a
X3
l
Terminal X3/28 = LOW
20
28
l
Identification is completed.
misc001
l
Calculated and stored:
– V/f rated frequency (C0015)
– Slip compensation (C0021)
– Motor stator inductance
Measured and stored:
l
– Motor stator resistance
Setting possibilities: (^ 148)
e. g. via potentiometer at the
terminals 7, 8, 9
X3
Terminal X3/28 = HIGH
20
28
misc002
CW rotation: X3/E4 = LOW
CCW rotation: X3/E4 = HIGH
If the drive does not start, press
U
EDK82EV113 DE/EN/FR 8.1
c
Off
high−pitched tone. The motor
does not rotate!
(C0092)
(C0084) = Total resistance of
motor cable and motor
L