The most important codes for commissioning
Selection
−650.00
{0.02 Hz}
0
Ready
1
Start identification
V/f−rated frequency (C0015), slip
l
compensation (C0021) and motor stator
inductivity (C0092) are calculated and
saved.
l
The motor stator resistance (C0084) =
total resistance of motor cable and
motor is measured and saved
C0050
Output frequency (MCTRL1−NOUT)
C0034
Analog setpoint selection range
C0007
Fixed configuration − digital input signals
C0010
Minimum output frequency
C0011
Maximum output frequency
C0012
Acceleration time main setpoint
C0013
Deceleration time main setpoint
C0015
V/f rated frequency
C0016
U
boost
min
C0002
Parameter set transfer
EDK82EV113 DE/EN/FR 8.1
7
Commissioning
IMPORTANT
j
650.00
l
Selection via function
of the
keypad or the parameter channel
l
Is added to main setpoint
l
Value is stored when switching the
mains or removing the keypad
Only when the motor is cold!
1. Inhibit controller, wait until drive is
in standstill
2. Enter the correct motor data under
C0087, C0088, C0089, C0090,
C0091 (see motor nameplate).
v
3. C0148 = set 1 by
4. Enable controller
The identification
c
– starts,
is off
– takes approx. 30 s
c
– is completed when
is on
again
5. Controller inhibit
l
After mains switching or when
g
using the function
the code
from C0517/1 will be displayed.
l
In Lenze setting, the user menu
contains the most important codes
for starting−up the control mode
"V/f characteristic control with
linear characteristic"
l
When the password protection is
activated, only the codes entered
under C0517 are freely accessible.
l
Enter the required code numbers in
the subcodes.
Codes, which are only active when
being used together with an
Application−I/O, cannot be entered!